background image

27

7.6.2 -  Reset

Reset.means.the.active.setpoint.is.modified.so.that.less.machine.

capacity is required. In the cooling mode the setpoint is increased, 

whereas.in.the.heating.mode.it.is.decreased..This.modification.is.

in general a reaction to a drop in the load.

The reset can be based on the following parameters:
• 

OAT that gives the measure of the load trends for the 
building

• 

Return water temperature  
(

Δ

T provides the average building load)

• 

Space temperature (EMM option)

• 

Dedicated 4-20 mA input

The.reset.source.and.the.reset.parameters.can.be.configured.in.

the Main menu (RESETCFG – Reset Configuration). In 
response to a drop in the reset source, the cooling setpoint is 
normally reset upwards to optimise unit performance.

The amount of reset is determined by linear interpolation 
based on the following parameters:
• 

A reference at which reset is zero (no reset value)

• 

A reference at which reset is maximum (full reset value)

• 

The maximum reset value

20

Reset based on OAT

25

0

Reset based on delta T

3

4

Reset based on analog input

20

no_reset

selection

full_reset

Legend: 

A: Maximum reset value

  B: Reference for zero reset

  C: Reference for maximum reset

  D: Building load

7.7 -   Capacity limitation

The Touch Pilot control system allows for the constant control 
of the unit capacity by setting its maximum allowable capacity. 

The main control system enables to limit the unit capacity 
using one of the external orders:
• 

By means of user-controlled volt-free contacts. Units 
without the energy management module have one 
contact. Units with the energy management module 
permit three capacity limitation levels (see also 
section 3.9.4). The unit capacity can never exceed the 
limit setpoint activated by these contacts. The limit 

setpoints.can.be.modified.in.the.SETPOINT.menu.

• 

By lag limit set by the master unit (master/slave assembly).

• 

By night mode limitation control. The demand limit 
value in the night mode is selectable if the value is 
below the selected limit. A limit value of 100% means 
that the unit can use all capacity stages.

In certain conditions, the unit power consumption can exceed 
the capacity limitation threshold to protect the compressors. 

7.8 -   Current limitation

Current limitation is used via the demand limit function. If 
the current limitation is active (

Current Limit Select

 in the 

GEN_CONF menu), the control calculates the sum of 
compressors current to obtain the total compressor current. 
If this value exceeds the pre-defined limit, the control 
commands a reduction of the compressor load, until it is 
below the limit again. Before loading a capacity stage, the 
control estimates the future total compressor current and 
ensures that it does not exceed the limit.
 
The current limit is based on two parameters:
• 

The current limit that corresponds to 100% capacity 
(

CurrentLimit at 100%

, GEN_CONF – General 

Configuration)

• 

The active demand limit determined either by the 
demand limit contact (see also section 3.9.4) or by the 
network (

Active Demand Limit Val

, GENUNIT – 

General Parameters)

Chiller current limit is displayed in the GENUNIT menu.

Current limitation is disabled if the unit operates in the 
master/slave mode, the unit is controlled by a System 
Manager or the night mode is active.

7.9 -   Capacity control

This function adjusts the capacity using the compressor slide 
valve to keep the water exchanger temperature at its setpoint. 
The control system continuously takes account of the 
temperature error with respect to the setpoint, the rate of 
change in this error and the difference between entering and 
leaving water temperatures in order to determine the optimal 
moment at which to add or withdraw capacity. 

Compressors are started and stopped in a sequence designed 
to equalise the number of start-ups (value weighted by their 
operating time). For more information about compressors 
sequence, see 

Balanced loading sequence

 and 

Staged loading 

sequence

 in section 7.13.

7.10 -  Night mode

Night.mode.allows.users.to.configure.the.unit.to.operate.with.
specific.parameters.in.a.specific.time.period..During.the.night.

period, the unit capacity is limited and the number of 
operating fans is reduced.

The.night.period.is.defined.by.a.start.time.and.an.end.time.

that are the same for each day of the week. The Night mode 

settings.or.the.maximum.capacity.value.can.be.configured..

via the Configuration menu (GEN_CONF – General 

Configuration)..

Only logged-in users can modify Night Mode settings (see 
also section 4.3.3).

Summary of Contents for 30XA-ZE

Page 1: ...CONTROLS MANUAL Operation instructions Original document Touch Pilot Control AquaForce PUREtec with R 1234ze E 30XA XAS XW 30XA ZE XW ZE...

Page 2: ...ace access 13 5 2 Web browser configuration 13 5 3 Technical documentation access 13 6 TOUCH PILOT INTERFACE DETAILS 14 6 1 Menu structure 14 6 2 Detailed menu description 15 6 3 Alarms menu 20 6 4 Co...

Page 3: ...7 21 Dry cooler option 30XW 31 7 22 Hydronic kit option 30XA 31 7 23 30XA ZE and 30XW ZE units HFO 31 7 24 High condensing temperature option 30XW 31 7 25 Maximum condenser leaving water temperature...

Page 4: ...recommended to ensure optimal operation of the equipment as well as the optimization of all available functionalities Note that this document may refer to optional components and certain functions op...

Page 5: ...ames with great care IMPORTANT Some specific safety precautions should be taken in case of HFO units For more information about handling the equipment safely please refer to the IOM Unit documentation...

Page 6: ...the boards otherwise the boards may be damaged In the event of a power supply interrupt the unit restarts automatically without the need for an external command However any faults active when the sup...

Page 7: ...eat reclaim option Suction gas temperature sensor This sensor is used to control the suction gas temperature It is located at the suction line of each compressor Discharge gas temperature sensor Thiss...

Page 8: ...unit Heat reclaim condenser flow status 30XA only SIOB Heat reclaim DI 01 J1 Used to verify the water flow on the condenser side Heat reclaim enable switch 30XA only SIOB Heat reclaim DI 02 J1 Used to...

Page 9: ...Setpoint NOTE The synoptic screen display may vary depending on pumps configuration 4 TOUCH PILOT CONTROL INTERFACE 4 1 General description Touch Pilot includes the 5 in touch screen allowing for easy...

Page 10: ...hutdown by pressing Confirm Stop or return to the previous screen by pressing the Back button Once the unit has been stopped the Synoptic screen will be displayed see also section 4 2 2 Shows the last...

Page 11: ...he necessary changes Press the Up Down buttons to navigate between the screens Once all the necessary modifications have been made press to confirm or to cancel changes 4 4 1 General parameters screen...

Page 12: ...e selected period will be presented in the form of the green band on the timeline Press to confirm or to cancel changes 1 Selection of the applicable days for the time schedule 2 Modification of the p...

Page 13: ...and use a direct connection NOTE Two users can be connected simultaneously with no priority between them The last modification is taken into account 5 3 Technical documentation access When theTouch P...

Page 14: ...14 6 TOUCH PILOT INTERFACE DETAILS 6 1 Menu structure...

Page 15: ...y Running Ready Override Tripout Test Runtest 3 0 to 1 Net Cmd Start Stop Unit start stop via Network 4 0 to 1 Net Cmd Occupied Unit time schedule via Network 5 min Minutes Left for Start Minutes befo...

Page 16: ...conomizer Gas Temp B Economizer gas temperature circuit B 28 C Economizer Gas Temp C Economizer gas temperature circuit C 29 C Dry Cool Leav Water Tmp Dry Cooler Leaving Water Temperature units fitted...

Page 17: ...own Indicator State Shutdown indicator status 21 0 to 100 Cond 3 Way Valve Pos Condenser 3 way valve position 22 off on Cooler Heater Command Evaporator heater command status 23 off on Ready or Runnin...

Page 18: ...s condenser pump 1 12 hour Condenser Pump 2 Hours Operating hours condenser pump 2 not available 13 hour Free Cool A Pump Hours Pump operating hours in Free Cooling circuit A 14 hour Free Cool B Pump...

Page 19: ...lve status circuit B Depends on the selected language English by default FREECOOL Free cooling No Status Unit Displayed text Description 1 GENERAL PARAMETERS GENERAL PARAMETERS 2 0 to 1 Free Cooling D...

Page 20: ...26 6 7 C Cooling Ice Setpoint Ice storage setpoint 4 0 1 to 11 1 0 6 C Cooling Ramp Loading Cooling ramp loading setpoint 5 26 7 to 63 37 8 C Heating Setpoint 1 Heating setpoint 1 6 26 7 to 63 37 8 C...

Page 21: ...6 1 to 15 1 min Unit Off to On Delay Unit Off to On delay 7 00 00 0 Night Mode Start Hour Night mode start time 8 00 00 0 Night Mode End Hour Night mode end time 9 0 to 100 100 Night Capacity Limit N...

Page 22: ...no reset value 8 10 to 51 7 10 C OAT Full Reset Value OAT max reset value 9 0 to 13 9 0 C Delta T No Reset Value Delta T no reset value 10 0 to 13 9 0 C Delta T Full Reset Value Delta T max reset valu...

Page 23: ...ek of the month Depends on the selected language English by default DATETIME Date Time configuration No Status Default Displayed text Description Date DD MM YY 1 1 to 31 Day of month Day of the month...

Page 24: ...en remote off active unoccupied remote off active disabled network off active unoccupied network off active local unoccupied local off active open remote remote off active remote unoccupied remote off...

Page 25: ...vailable the unit is stopped and started again with the second pump If there is no pump available the unit shuts down Units are fitted with the flow switch allowing for the water flow control For more...

Page 26: ...eating setpoint 2 heating auto occupied heating setpoint 1 heating auto unoccupied heating setpoint 2 Any configuration default configuration REMOTE OPERATING TYPE Parameter status Active setpoint Hea...

Page 27: ...dtoprotectthecompressors 7 8 Current limitation Current limitation is used via the demand limit function If the current limitation is active Current Limit Select in the GEN_CONF menu the control calcu...

Page 28: ...units This function determines in which order the circuit capacity is changed Compressor loading is managed by starting stopping the compressors and controlling the position of the slide valve Two ty...

Page 29: ...95 35 0 0 100 100 95 30 0 0 100 100 100 0 0 0 Loading sequence Unloading sequence Lead circ Lag circ 1 Lag circ 2 Lead circ Lag circ 1 Lag circ 2 0 0 0 100 100 100 30 0 0 100 100 95 35 0 0 100 100 90...

Page 30: ...he contact is closed the unit enters the ice storage mode Space temperature AI 01 J25 Analogue input Active setpoint reset via space temperature control Capacity limit control AI 10 J9 Analogue input...

Page 31: ...g Full Load Timeout when the water temperature setpoint is not reached Full Load Timeout GEN_CONF General Configuration 7 21 Dry cooler option 30XW 30XW units may come with the dry cooler option that...

Page 32: ...6 holiday periods Each period is defined by three parameters the month the start day and the duration of the holiday period During the holiday periods the controller will be in occupied or unoccupied...

Page 33: ...ight part of the screen and then select Current Alarms 8 4 Resetting alarms Touch Pilot control distinguishes between two types of alarms General alarms are used to indicate pumps failure transducers...

Page 34: ...ove As above As above 24 15026 Economizer gas thermistor fault circuit C As above As above As above 25 15030 Free cooling liquid thermistor fault circuit A As above Free cooling disabled As above 26 1...

Page 35: ...ump is running Discharge pressure transducer defective refrigerant leak or low condenser water temperature 80 10003 Condenser frost protection circuit B As above Circuit B shuts down but the pump is r...

Page 36: ...uit A Manual None Defective or incorrectly wired solenoid valves defective current transformer 132 10088 Slide valve control unverifiable circuit B Manual None As above 133 10089 Slide valve control u...

Page 37: ...temperature and the VFD fan 67 Alarm Option configuration has changed Contact Carrier Service 68 Alarm Emergency stop Contact Carrier Service 71 Alarm PTC 1 emergency stop Contact Carrier Service 72 A...

Page 38: ...rvice 8 Alert DC undervoltage Contact Carrier Service 9 Alert Inverter overloaded Check the VFD output current 10 Alert Motor overtemperature Check the motor temperature 11 Alert Motor thermistor Cont...

Page 39: ...No 13453 07 2016 Supersedes order No 13453 03 2016 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Reviews: