18
PUMPSTAT – Pump status
No.
Status
Unit
Displayed text*
Description
1
no/yes
-
Cooler Flow Setpoint Out
Evaporator flow setpoint output
2
0 to 1
-
Cooler Pump #1 Command
Evaporator pump 1 control
3
0 to 1
-
Cooler Pump #2 Command
Evaporator pump 2 control
4
0 to 1
-
Rotate Cooler Pumps ?
Evaporator pumps rotation
5
open/close
-
Cooler Flow Switch
Evaporator flow switch
6
0 to 1
-
Condenser Pump Command1
Condenser pump 1 control
7
0 to 1
-
Condenser Pump Command2
Condenser pump 2 control (not available!)
8
0 to 1
-
Rotate Condenser Pumps ?
Condenser pumps rotation (not available!)
9
-
kPa
Water pres before cooler
Evaporator entering water pressure
10
-
kPa
Water pres after cooler
Evaporator leaving water pressure
11
-
kPa
Water pres before filter
Filter entering water pressure
12
-
kPa
Water pres after filter
Filter leaving water pressure
13
-
l/s
Water flow
Water flow rate
14
-
kW
Cooling power
Cooling power
15
open/close
-
Condenser Flow Status
Condenser flow status
*Depends on the selected language (English by default).
RUNTIME – Run times
No.
Status
Unit
Displayed text*
Description
1
-
hour
Machine Operating Hours
Unit operating hours
2
-
-
Machine Starts Number
Number of unit starts
3
-
hour
Compressor A Hours
Operating hours, compressor A
4
-
-
Compressor A Starts
Number of starts, compressor A
5
-
hour
Compressor B Hours
Operating hours, compressor B
6
-
-
Compressor B Starts
Number of starts, compressor B
7
-
hour
Compressor C Hours
Operating hours, compressor C
8
-
-
Compressor C Starts
Number of starts, compressor C
9
-
hour
Cooler Pump #1 Hours
Operating hours, evaporator pump 1
10
-
hour
Cooler Pump #2 Hours
Operating hours, evaporator pump 2
11
-
hour
Condenser Pump #1 Hours
Operating hours, condenser pump 1
12
-
hour
Condenser Pump #2 Hours
Operating hours, condenser pump 2 (not available!)
13
-
hour
Free Cool A Pump Hours
Pump operating hours in Free Cooling, circuit A
14
-
hour
Free Cool B Pump Hours
Pump operating hours in Free Cooling, circuit B
* Depends on the selected language (English by default).
NOTE:
The displayed run times are updated every hour.
MODES – Modes
No.
Status
Unit
Displayed text*
Description
1
no/yes
-
Start Up Delay In Effect
Start-up delay in effect
2
no/yes
-
Second Setpoint In Use
Second setpoint in use
3
no/yes
-
Reset In Effect
Setpoint reset active
4
no/yes
-
Demand limit Active
Demand limit active
5
no/yes
-
Ramp Loading Active
Ramp loading active
6
no/yes
-
Cooler Heater Active
Evaporator heater active
7
no/yes
-
Cooler Pump Rotation
Evaporator pump rotation
8
no/yes
-
Pump Periodic Start
Pump periodic start active
9
no/yes
-
Night Low Noise Active
Night low noise active
10
no/yes
-
Master Slave Active
Master/slave mode active
11
no/yes
-
Auto Changeover Active
Automatic changeover active
12
no/yes
-
Heating Low EWT Lockout
Heating low EWT lockout
13
no/yes
-
Condenser Pump Rotation
Condenser pump rotation (not available!)
14
no/yes
-
Cond Pump Periodic Start
Condenser pump periodic start
15
no/yes
-
Ice Mode In Effect
Ice storage mode active
16
no/yes
-
Defrost Active On Cir A
Defrost mode active, circuit A
17
no/yes
-
Defrost Active On Cir B
Defrost mode active, circuit B
18
no/yes
-
Free Cooling Active
Free cooling mode active
19
no/yes
-
Reclaim Active
Reclaim mode active
20
no/yes
-
Low Suction Circuit A
Low suction, circuit A
21
no/yes
-
Low Suction Circuit B
Low suction, circuit B
22
no/yes
-
Low Suction Circuit C
Low suction, circuit C
23
no/yes
-
Map compressor Circuit A
Compressor mapping, circuit A
24
no/yes
-
Map compressor Circuit B
Compressor mapping, circuit B
25
no/yes
-
Map compressor Circuit C
Compressor mapping, circuit C