7.6 - Control point
The control point represents the water temperature that the
unit must produce. It enables to decrease the required
capacity depending on the unit load operating conditions.
Control point = Active se Reset
The control point is calculated based on the active setpoint
and the reset calculation. The forced value can be used
instead of any other setpoint calculation only when the unit
is in the Network operating type.
7.6.1 - Active setpoint
Two setpoints can be selected. Depending on the current
operation type, the active setpoint can be selected manually
in the Main menu (GENUNIT – General Parameters), with
the volt-free user contacts, with network commands (CCN
or BACnet) or automatically with the setpoint time schedule
(schedule 2).
LOCAL OPERATING TYPE
Parameter status
Active setpoint
Heating/cooling
operating mode
Setpoint selection Heating/Cooling
selection in local mode
Ice storage
configuration
Setpoint switch
Schedule 2 status
cooling
csp1
-
*
*
-
cooling setpoint 1
cooling
csp2
no
*
*
-
cooling setpoint 2
cooling
csp2
yes
closed
*
cooling setpoint 2
cooling
csp2
yes
open
*
ice storage setpoint
cooling
auto
-
*
*
occupied
cooling setpoint 1
cooling
auto
no
*
*
unoccupied
cooling setpoint 2
cooling
auto
yes
closed
*
unoccupied
cooling setpoint 2
cooling
auto
yes
open
*
unoccupied
ice storage setpoint
heating
hsp1
-
*
*
-
heating setpoint 1
heating
hsp2
-
*
*
-
heating setpoint 2
heating
auto
-
*
*
occupied
heating setpoint 1
heating
auto
-
*
*
unoccupied
heating setpoint 2
*Any configuration, (-) default configuration.
REMOTE OPERATING TYPE
Parameter status
Active setpoint
Heating/cooling
operating mode
Setpoint selection
Ice storage configuration
Ice done contact
Setpoint switch
Schedule 2 status
cooling
-
-
*
open
-
cooling setpoint 1
cooling
-
no
*
closed
-
cooling setpoint 2
cooling
-
yes
closed
closed
-
cooling setpoint 2
cooling
-
yes
open
closed
-
ice storage setpoint
heating
-
-
*
open
-
heating setpoint 1
heating
-
-
*
closed
-
heating setpoint 2
*Any configuration, (-) default configuration.
NETWORK OPERATING TYPE
Parameter status
Active setpoint
Heating/cooling
operating mode
Setpoint selection
Ice storage configuration
Ice done contact
Setpoint switch
Schedule 2 status
cooling
-
-
*
*
occupied
cooling setpoint 1
cooling
-
-
*
*
unoccupied
cooling setpoint 2
heating
-
-
*
*
occupied
heating setpoint 1
heating
-
-
*
*
unoccupied
heating setpoint 2
*Any configuration, (-) default configuration.
NOTE:
Ice storage configuration and ice done contact apply only to units with the optional energy management module.
The following tables summarise possible selections depending
on the control type (Local, Remote or Network) and the
following parameters:
•
Heating or Cooling operating mode:
Heat/Cool select
(GENUNIT menu)
•
Setpoint selected via the Touch Pilot user interface:
Setpoint select permits selection of the active setpoint
if the unit is in the Local operating type (GENUNIT
menu)
•
Setpoint switch status:
Remote setpoint switch
(INPUTS menu)
•
Schedule 2 status:
Schedule for setpoint selection