15
6.2 - Detailed menu description
Icon
Displayed text*
Description
Associated table
General Parameters
General parameters
GENUNIT
Temperatures
Temperatures
TEMP
Pressures
Pressures
PRESSURE
Inputs Status
Inputs status
INPUTS
Outputs Status
Outputs status
OUTPUTS
Pump Status
Pump status
PUMPSTAT
Run Times
Run times
RUNTIME
Modes
Modes
MODES
Reclaim
Reclaim
RECLAIM
Freecooling
Free cooling
FREECOOL
Setpoint Table
Setpoint table
SETPOINT
Trendings
Trendings
TRENDING
Configuration Menu
Configuration menu
CONFIG
* Depends on the selected language (English by default).
GENUNIT – General parameters
No.
Status
Unit
Displayed text*
Description
1
0 to 3
-
Local=0 Net.=1 Remote=2
Operating mode:
0 = Local
1 = Network
2 = Remote
2
-
-
Run Status
Unit running status: Off, Stopping, Delay,
Running, Ready, Override, Tripout, Test, Runtest
3
0 to 1
-
Net.: Cmd Start/Stop
Unit start/stop via Network
4
0 to 1
-
Net.: Cmd Occupied
Unit time schedule via Network
5
-
min
Minutes Left for Start
Minutes before the unit start-up
6
-
-
Heat/Cool status
Heating/cooling status
7
0 to 2
-
Heat/Cool Select
Heating/cooling selection
8
-
-
0=Cool. 1=Heat. 2=Auto
0 = Cooling
1 = Heating
2 = Automatic heating/cooling control
9
0 to 2
-
Setpoint Select
Setpoint selection
10
-
-
0=Auto. 1=Spt1. 2=Spt2
0 = Automatic setpoint selection
1 = Setpoint 1
2 = Setpoint 2
11
0 to 1
-
Setpoint Occupied?
Setpoint status
12
0 to 100
%
Percent Total Capacity
Total unit capacity
13
-
A
Actual Chiller Current
Actual chiller current
14
0 to 200
A
Chiller Current Limit
Chiller current limit
15
-
°C
Current Setpoint
Current setpoint value
16
-
-
Control Point
Control point
17
0 to 1
-
Emergency Stop
Emergency stop
18
0 to 100
%
Active Demand Limit Val
Active demand limit value
* Depends on the selected language (English by default)