COMMUNICATION FAILURE

54

4101

Communication  loss  with  Compressor  Board  A                 Automatic, if 

communication is 

re-established

Unit shuts down

Bus installation fault or 

defective board

55

4201

Communication  loss  with  Compressor  Board  B                  As above

Unit shuts down

As above

56

4301

Communication  loss  with  Compressor  Board  C                 As above

Unit shuts down

As above

57

4901

Communication loss with SIOB Board Number 1 As above

Unit shuts down

As above

58

4902

Communication loss with SIOB Board Number 2 As above

Unit shuts down

As above

59

4903

Communication loss with SIOB Board Number 3 As above

Unit shuts down

As above

60

4904

Communication loss with SIOB Board Number 4 As above

Unit shuts down

As above

61

4905

Communication loss with SIOB Board Number 5 As above

Unit shuts down

As above

62

4906

Communication loss with SIOB Board Number 6 As above

Unit shuts down

As above

63

4501

Communication loss with Fan Board Number 1

As above

Circuit A shuts down

As above

64

4502

Communication loss with Fan Board Number 2

As above

Circuit B shuts down

As above

65

4503

Communication loss with Fan Board Number 3

As above

Circuit C shuts down

As above

66

4801

Communication loss with VLT Board Number 1, 

(units w/o option 17)

As above

Circuit A shuts down

As above

67

4802

Communication loss with VLT Board Number 2, 

(units w/o option 17)

As above

Circuit B shuts down

As above

68

4803

Communication loss with VLT Board Number 3, 

(units w/o option 17)

As above

Circuit C shuts down

As above

69

4704

Loss of communication with Fan VLT Drive Board 

A1 (option 17)

As above

Circuit A shuts down

As above

70

4705

Loss of communication with Fan VLT Drive Board 

A2 (option 17)

As above

Circuit A shuts down

As above

71

4706

Loss of communication with Fan VLT Drive Board 

A3 (option 17)

As above

Circuit A shuts down

As above

72

4707

Loss of communication with Fan VLT Drive Board 

B1 (option 17)

As above

Circuit B shuts down

As above

73

4708

Loss of communication with Fan VLT Drive Board 

B2 (option 17)

As above

Circuit B shuts down

As above

74

4709

Loss of communication with Fan VLT Drive Board 

B3 (option 17)

As above

Circuit B shuts down

As above

PROCESS FAILURE

78

10001

Evaporator frost protection

Manual

Unit shuts down, but the pump 

continues to run

No water flow,

defective thermistor

79

10002

Condenser frost protection, circuit A

Automatic 

(if saturated discharge 

temperature is more 

than 4.4°C) or Manual

Circuit A shuts down, but the pump 

is running

Discharge pressure 

transducer defective, 

refrigerant leak or low 

condenser water temperature

80

10003

Condenser frost protection, circuit B

As above

Circuit B shuts down, but the pump 

is running

As above

81

10004

Condenser frost protection, circuit C

As above

Circuit C shuts down, but the pump 

is running

As above

82

10005

Low suction temperature, circuit A

Automatic (the first 

alarm in the last 24 

hours) or Manual

Circuit A shuts down

Pressure sensor defective, 

EXV blocked or lack of 

refrigerant

83

10006

Low suction temperature, circuit B

As above

Circuit B shuts down

As above

84

10007

Low suction temperature, circuit C

As above

Circuit C shuts down

As above

85

10008

High superheat, circuit A

Manual 

Circuit A shuts down

As above

86

10009

High superheat, circuit B

Manual

Circuit B shuts down

As above

87

10010

High superheat, circuit C

Manual

Circuit C shuts down

As above

88

10011

Low superheat, circuit A

Manual

Circuit A shuts down

As above

89

10012

Low superheat, circuit B

Manual

Circuit B shuts down

As above

90

10013

Low superheat, circuit C

Manual

Circuit C shuts down

As above

91

10014

Customer safety loop failure

Automatic (the first 

alarm in the last 24 

hours) or Manual

Unit shuts down

Customer interlock closed

92

10028

Electrical box thermostat

Automatic

Unit shuts down

Electrical box fault: Control 

box poorly ventilated or poor 

electrical connection

93

10029

System manager communication fault

Automatic, if 

communication is 

re-established

Unit returns to the stand-alone 

mode

CCN bus installation 

defective

94

10030

Master/slave communication failure

Automatic

Master/slave control disabled

As above

110

10031

Emergency stop 

Automatic

Unit shuts down

Network emergency stop 

command

111

10032

Evaporator pump 1 fault 

Manual

Unit is restarted with another pump 

running. If no pumps are available, 

the unit shuts down

Pump overheats or poor 

pump connection

112

10033

Evaporator pump 2 fault 

Manual

As above

As above

113

10015

Flow controller fault - condenser flow switch failure

Automatic (the first 

alarm in the last 24 

hours) or Manual

Condenser pump is stopped

Condenser flow switch open

114

10034

Reclaim operation failure, circuit A

Manual

Circuit A returns to the air-cooled 

mode

Low condenser flow

115

10035

Reclaim operation failure, circuit B

Manual

Circuit B returns to the air-cooled 

mode

As above

116

10037

High condensing temperature, circuit A

Automatic

Circuit A shuts down

Defective transducer

117

10038

High condensing temperature, circuit B

Automatic

Circuit B shuts down

As above

118

10039

High condensing temperature, circuit C

Automatic

Circuit C shuts down

As above

Summary of Contents for 30XA-ZE

Page 1: ...CONTROLS MANUAL Operation instructions Original document Touch Pilot Control AquaForce PUREtec with R 1234ze E 30XA XAS XW 30XA ZE XW ZE...

Page 2: ...ace access 13 5 2 Web browser configuration 13 5 3 Technical documentation access 13 6 TOUCH PILOT INTERFACE DETAILS 14 6 1 Menu structure 14 6 2 Detailed menu description 15 6 3 Alarms menu 20 6 4 Co...

Page 3: ...7 21 Dry cooler option 30XW 31 7 22 Hydronic kit option 30XA 31 7 23 30XA ZE and 30XW ZE units HFO 31 7 24 High condensing temperature option 30XW 31 7 25 Maximum condenser leaving water temperature...

Page 4: ...recommended to ensure optimal operation of the equipment as well as the optimization of all available functionalities Note that this document may refer to optional components and certain functions op...

Page 5: ...ames with great care IMPORTANT Some specific safety precautions should be taken in case of HFO units For more information about handling the equipment safely please refer to the IOM Unit documentation...

Page 6: ...the boards otherwise the boards may be damaged In the event of a power supply interrupt the unit restarts automatically without the need for an external command However any faults active when the sup...

Page 7: ...eat reclaim option Suction gas temperature sensor This sensor is used to control the suction gas temperature It is located at the suction line of each compressor Discharge gas temperature sensor Thiss...

Page 8: ...unit Heat reclaim condenser flow status 30XA only SIOB Heat reclaim DI 01 J1 Used to verify the water flow on the condenser side Heat reclaim enable switch 30XA only SIOB Heat reclaim DI 02 J1 Used to...

Page 9: ...Setpoint NOTE The synoptic screen display may vary depending on pumps configuration 4 TOUCH PILOT CONTROL INTERFACE 4 1 General description Touch Pilot includes the 5 in touch screen allowing for easy...

Page 10: ...hutdown by pressing Confirm Stop or return to the previous screen by pressing the Back button Once the unit has been stopped the Synoptic screen will be displayed see also section 4 2 2 Shows the last...

Page 11: ...he necessary changes Press the Up Down buttons to navigate between the screens Once all the necessary modifications have been made press to confirm or to cancel changes 4 4 1 General parameters screen...

Page 12: ...e selected period will be presented in the form of the green band on the timeline Press to confirm or to cancel changes 1 Selection of the applicable days for the time schedule 2 Modification of the p...

Page 13: ...and use a direct connection NOTE Two users can be connected simultaneously with no priority between them The last modification is taken into account 5 3 Technical documentation access When theTouch P...

Page 14: ...14 6 TOUCH PILOT INTERFACE DETAILS 6 1 Menu structure...

Page 15: ...y Running Ready Override Tripout Test Runtest 3 0 to 1 Net Cmd Start Stop Unit start stop via Network 4 0 to 1 Net Cmd Occupied Unit time schedule via Network 5 min Minutes Left for Start Minutes befo...

Page 16: ...conomizer Gas Temp B Economizer gas temperature circuit B 28 C Economizer Gas Temp C Economizer gas temperature circuit C 29 C Dry Cool Leav Water Tmp Dry Cooler Leaving Water Temperature units fitted...

Page 17: ...own Indicator State Shutdown indicator status 21 0 to 100 Cond 3 Way Valve Pos Condenser 3 way valve position 22 off on Cooler Heater Command Evaporator heater command status 23 off on Ready or Runnin...

Page 18: ...s condenser pump 1 12 hour Condenser Pump 2 Hours Operating hours condenser pump 2 not available 13 hour Free Cool A Pump Hours Pump operating hours in Free Cooling circuit A 14 hour Free Cool B Pump...

Page 19: ...lve status circuit B Depends on the selected language English by default FREECOOL Free cooling No Status Unit Displayed text Description 1 GENERAL PARAMETERS GENERAL PARAMETERS 2 0 to 1 Free Cooling D...

Page 20: ...26 6 7 C Cooling Ice Setpoint Ice storage setpoint 4 0 1 to 11 1 0 6 C Cooling Ramp Loading Cooling ramp loading setpoint 5 26 7 to 63 37 8 C Heating Setpoint 1 Heating setpoint 1 6 26 7 to 63 37 8 C...

Page 21: ...6 1 to 15 1 min Unit Off to On Delay Unit Off to On delay 7 00 00 0 Night Mode Start Hour Night mode start time 8 00 00 0 Night Mode End Hour Night mode end time 9 0 to 100 100 Night Capacity Limit N...

Page 22: ...no reset value 8 10 to 51 7 10 C OAT Full Reset Value OAT max reset value 9 0 to 13 9 0 C Delta T No Reset Value Delta T no reset value 10 0 to 13 9 0 C Delta T Full Reset Value Delta T max reset valu...

Page 23: ...ek of the month Depends on the selected language English by default DATETIME Date Time configuration No Status Default Displayed text Description Date DD MM YY 1 1 to 31 Day of month Day of the month...

Page 24: ...en remote off active unoccupied remote off active disabled network off active unoccupied network off active local unoccupied local off active open remote remote off active remote unoccupied remote off...

Page 25: ...vailable the unit is stopped and started again with the second pump If there is no pump available the unit shuts down Units are fitted with the flow switch allowing for the water flow control For more...

Page 26: ...eating setpoint 2 heating auto occupied heating setpoint 1 heating auto unoccupied heating setpoint 2 Any configuration default configuration REMOTE OPERATING TYPE Parameter status Active setpoint Hea...

Page 27: ...dtoprotectthecompressors 7 8 Current limitation Current limitation is used via the demand limit function If the current limitation is active Current Limit Select in the GEN_CONF menu the control calcu...

Page 28: ...units This function determines in which order the circuit capacity is changed Compressor loading is managed by starting stopping the compressors and controlling the position of the slide valve Two ty...

Page 29: ...95 35 0 0 100 100 95 30 0 0 100 100 100 0 0 0 Loading sequence Unloading sequence Lead circ Lag circ 1 Lag circ 2 Lead circ Lag circ 1 Lag circ 2 0 0 0 100 100 100 30 0 0 100 100 95 35 0 0 100 100 90...

Page 30: ...he contact is closed the unit enters the ice storage mode Space temperature AI 01 J25 Analogue input Active setpoint reset via space temperature control Capacity limit control AI 10 J9 Analogue input...

Page 31: ...g Full Load Timeout when the water temperature setpoint is not reached Full Load Timeout GEN_CONF General Configuration 7 21 Dry cooler option 30XW 30XW units may come with the dry cooler option that...

Page 32: ...6 holiday periods Each period is defined by three parameters the month the start day and the duration of the holiday period During the holiday periods the controller will be in occupied or unoccupied...

Page 33: ...ight part of the screen and then select Current Alarms 8 4 Resetting alarms Touch Pilot control distinguishes between two types of alarms General alarms are used to indicate pumps failure transducers...

Page 34: ...ove As above As above 24 15026 Economizer gas thermistor fault circuit C As above As above As above 25 15030 Free cooling liquid thermistor fault circuit A As above Free cooling disabled As above 26 1...

Page 35: ...ump is running Discharge pressure transducer defective refrigerant leak or low condenser water temperature 80 10003 Condenser frost protection circuit B As above Circuit B shuts down but the pump is r...

Page 36: ...uit A Manual None Defective or incorrectly wired solenoid valves defective current transformer 132 10088 Slide valve control unverifiable circuit B Manual None As above 133 10089 Slide valve control u...

Page 37: ...temperature and the VFD fan 67 Alarm Option configuration has changed Contact Carrier Service 68 Alarm Emergency stop Contact Carrier Service 71 Alarm PTC 1 emergency stop Contact Carrier Service 72 A...

Page 38: ...rvice 8 Alert DC undervoltage Contact Carrier Service 9 Alert Inverter overloaded Check the VFD output current 10 Alert Motor overtemperature Check the motor temperature 11 Alert Motor thermistor Cont...

Page 39: ...No 13453 07 2016 Supersedes order No 13453 03 2016 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Reviews: