Alarm No. Alarm code Alarm description

Reset type

Action taken 

Possible cause

122

10043

Low entering water temperature in heating

Automatic, if EWT returns to 

normal or Heating mode is 

disabled

None

Entering water temperature 

is below 3.3°C

95

10067

Low oil pressure, circuit A

Manual

Circuit A shuts down

Pressure sensor fault, 

defective wiring or oil filter 

installation fault

96

10068

Low oil pressure, circuit B

Manual

Circuit B shuts down

As above

97

10069

Low oil pressure, circuit C

Manual

Circuit C shuts down

As above

98

10070

Maximum oil filter differential pressure,

 

 circuit A

Manual

The affected compressor is stopped, 

other compressors continue to run

As above

99

10071

Maximum oil filter differential pressure, 

 

circuit B

Manual

As above

As above

100

10072

Maximum oil filter differential pressure, 

 

circuit C

Manual

As above

As above

123

10073

Condenser pump 1 fault

Manual

Unit is restarted with another pump 

running. If no pumps are available, 

the unit shuts down

Pump overheats or poor 

pump connection

124

10074

Condenser pump 2 fault (not available!)

Manual

As above

As above

104

10075

Low oil level, circuit A

Automatic (three alarms in 

the last 24 hours) or Manual

Circuit A shuts down

Oil level too low or oil level 

detector defective

105

10076

Low oil level, circuit B

As above

Circuit B shuts down

As above

106

10077

Low oil level, circuit C

As above

Circuit C shuts down

As above

125

10078

High discharge gas temperature, circuit A

Manual

Circuit A shuts down

Defective transducer, max. 

condensing temperature 

setpoint too low or 

refrigerant charge too high

126

10079

High discharge gas temperature, circuit B

Manual

Circuit B shuts down

As above

127

10080

High discharge gas temperature, circuit C

Manual

Circuit C shuts down

As above

128

10081

Suction valve closed, circuit A

Manual

Circuit A shuts down

Economizer pressure 

transducer defective, 

suction valve fault

129

10082

Suction valve closed, circuit B

Manual

Circuit B shuts down

As above

130

10083

Suction valve closed, circuit C

Manual

Circuit C shuts down

As above

101

10084

High oil filter drop pressure, circuit A

Manual

None

Pressure sensor fault, wiring 

defective, oil filter installation 

fault

102

10085

High oil filter drop pressure, circuit B

Manual

None

As above

103

10086

High oil filter drop pressure, circuit C

Manual

None

As above

131

10087

Slide valve control unverifiable, circuit A

Manual

None

Defective or incorrectly 

wired solenoid valves, 

defective current 

transformer

132

10088

Slide valve control unverifiable, circuit B

Manual

None

As above

133

10089

Slide valve control unverifiable, circuit C

Manual

None

As above

134

10090

Flow controller configuration fault

Manual

Unit is not allowed to restart

Defective flow controller or

wiring error

135

10091

Flow controller fault – evaporator flow switch

failure

Automatic (the first

alarm in the last 24

hours) or Manual

Compressors and the evaporator

pump are stopped

As above

137

10094

Free cooling operation failure, circuit A

Automatic (three alarms in 

the last 24 hours) or Manual

Circuit A shuts down, Free cooling 

can be started 30 minutes later

Refrigerant pump fault

138

10095

Free cooling operation failure, circuit B

As above

Circuit B shuts down, Free cooling 

can be started 30 minutes later

As above

139

10097

Water exchanger temperature sensors 

swapped

Manual

Unit shuts down

Leaving water temperature 

is higher than entering water 

temperature

136

10100

Electrical box fan failure

(units with HFO only)

Manual 

Unit shuts down

Electrical box fan 

malfunction or fan current 

probe malfunction

MAINTENANCE ALARMS

140

13-nnn

Service maintenance alert

Manual

None

Preventive maintenance 

date has passed

VLT DRIVE FAILURE

141

20-nnn

Variable speed controller error, circuit A 

(units w/o option 17)

Manual

Circuit A shuts down

Speed controller fault (see 

section 8.6.2)

142

23-nnn

Variable speed controller error, circuit B 

(units w/o option 17)

Manual

Circuit B shuts down

As above

143

26-nnn

Variable speed controller error, circuit C 

(units w/o option 17)

Manual

Circuit C shuts down

As above

144

20-nnn

VLT Fan Drive A1 Failure (option 17)

Manual

Circuit A shuts down

As above

145

21-nnn

VLT Fan Drive A2 Failure (option 17)

Manual

Circuit A shuts down

As above

146

22-nnn

VLT Fan Drive A3 Failure (option 17)

Manual

Circuit A shuts down

As above

147

23-nnn

VLT Fan Drive B1 Failure (option 17)

Manual

Circuit B shuts down

As above

148

24-nnn

VLT Fan Drive B2 Failure (option 17)

Manual

Circuit B shuts down

As above

149

25-nnn

VLT Fan Drive B3 Failure (option 17)

Manual

Circuit B shuts down

As above

153

34-nnn

Variable speed controller alert, circuit A 

(units w/o option 17)

Manual

None

Speed controller alert  

(see section 8.6.2)

154

35-nnn

Variable speed controller alert, circuit B 

(units w/o option 17)

Manual

None

As above

155

36-nnn

Variable speed controller alert, circuit C 

(units w/o option 17)

Manual

None

As above

156

38-nnn

Variable speed controller A1 alert (option 17) Automatic

None

As above

Summary of Contents for 30XA-ZE

Page 1: ...CONTROLS MANUAL Operation instructions Original document Touch Pilot Control AquaForce PUREtec with R 1234ze E 30XA XAS XW 30XA ZE XW ZE...

Page 2: ...ace access 13 5 2 Web browser configuration 13 5 3 Technical documentation access 13 6 TOUCH PILOT INTERFACE DETAILS 14 6 1 Menu structure 14 6 2 Detailed menu description 15 6 3 Alarms menu 20 6 4 Co...

Page 3: ...7 21 Dry cooler option 30XW 31 7 22 Hydronic kit option 30XA 31 7 23 30XA ZE and 30XW ZE units HFO 31 7 24 High condensing temperature option 30XW 31 7 25 Maximum condenser leaving water temperature...

Page 4: ...recommended to ensure optimal operation of the equipment as well as the optimization of all available functionalities Note that this document may refer to optional components and certain functions op...

Page 5: ...ames with great care IMPORTANT Some specific safety precautions should be taken in case of HFO units For more information about handling the equipment safely please refer to the IOM Unit documentation...

Page 6: ...the boards otherwise the boards may be damaged In the event of a power supply interrupt the unit restarts automatically without the need for an external command However any faults active when the sup...

Page 7: ...eat reclaim option Suction gas temperature sensor This sensor is used to control the suction gas temperature It is located at the suction line of each compressor Discharge gas temperature sensor Thiss...

Page 8: ...unit Heat reclaim condenser flow status 30XA only SIOB Heat reclaim DI 01 J1 Used to verify the water flow on the condenser side Heat reclaim enable switch 30XA only SIOB Heat reclaim DI 02 J1 Used to...

Page 9: ...Setpoint NOTE The synoptic screen display may vary depending on pumps configuration 4 TOUCH PILOT CONTROL INTERFACE 4 1 General description Touch Pilot includes the 5 in touch screen allowing for easy...

Page 10: ...hutdown by pressing Confirm Stop or return to the previous screen by pressing the Back button Once the unit has been stopped the Synoptic screen will be displayed see also section 4 2 2 Shows the last...

Page 11: ...he necessary changes Press the Up Down buttons to navigate between the screens Once all the necessary modifications have been made press to confirm or to cancel changes 4 4 1 General parameters screen...

Page 12: ...e selected period will be presented in the form of the green band on the timeline Press to confirm or to cancel changes 1 Selection of the applicable days for the time schedule 2 Modification of the p...

Page 13: ...and use a direct connection NOTE Two users can be connected simultaneously with no priority between them The last modification is taken into account 5 3 Technical documentation access When theTouch P...

Page 14: ...14 6 TOUCH PILOT INTERFACE DETAILS 6 1 Menu structure...

Page 15: ...y Running Ready Override Tripout Test Runtest 3 0 to 1 Net Cmd Start Stop Unit start stop via Network 4 0 to 1 Net Cmd Occupied Unit time schedule via Network 5 min Minutes Left for Start Minutes befo...

Page 16: ...conomizer Gas Temp B Economizer gas temperature circuit B 28 C Economizer Gas Temp C Economizer gas temperature circuit C 29 C Dry Cool Leav Water Tmp Dry Cooler Leaving Water Temperature units fitted...

Page 17: ...own Indicator State Shutdown indicator status 21 0 to 100 Cond 3 Way Valve Pos Condenser 3 way valve position 22 off on Cooler Heater Command Evaporator heater command status 23 off on Ready or Runnin...

Page 18: ...s condenser pump 1 12 hour Condenser Pump 2 Hours Operating hours condenser pump 2 not available 13 hour Free Cool A Pump Hours Pump operating hours in Free Cooling circuit A 14 hour Free Cool B Pump...

Page 19: ...lve status circuit B Depends on the selected language English by default FREECOOL Free cooling No Status Unit Displayed text Description 1 GENERAL PARAMETERS GENERAL PARAMETERS 2 0 to 1 Free Cooling D...

Page 20: ...26 6 7 C Cooling Ice Setpoint Ice storage setpoint 4 0 1 to 11 1 0 6 C Cooling Ramp Loading Cooling ramp loading setpoint 5 26 7 to 63 37 8 C Heating Setpoint 1 Heating setpoint 1 6 26 7 to 63 37 8 C...

Page 21: ...6 1 to 15 1 min Unit Off to On Delay Unit Off to On delay 7 00 00 0 Night Mode Start Hour Night mode start time 8 00 00 0 Night Mode End Hour Night mode end time 9 0 to 100 100 Night Capacity Limit N...

Page 22: ...no reset value 8 10 to 51 7 10 C OAT Full Reset Value OAT max reset value 9 0 to 13 9 0 C Delta T No Reset Value Delta T no reset value 10 0 to 13 9 0 C Delta T Full Reset Value Delta T max reset valu...

Page 23: ...ek of the month Depends on the selected language English by default DATETIME Date Time configuration No Status Default Displayed text Description Date DD MM YY 1 1 to 31 Day of month Day of the month...

Page 24: ...en remote off active unoccupied remote off active disabled network off active unoccupied network off active local unoccupied local off active open remote remote off active remote unoccupied remote off...

Page 25: ...vailable the unit is stopped and started again with the second pump If there is no pump available the unit shuts down Units are fitted with the flow switch allowing for the water flow control For more...

Page 26: ...eating setpoint 2 heating auto occupied heating setpoint 1 heating auto unoccupied heating setpoint 2 Any configuration default configuration REMOTE OPERATING TYPE Parameter status Active setpoint Hea...

Page 27: ...dtoprotectthecompressors 7 8 Current limitation Current limitation is used via the demand limit function If the current limitation is active Current Limit Select in the GEN_CONF menu the control calcu...

Page 28: ...units This function determines in which order the circuit capacity is changed Compressor loading is managed by starting stopping the compressors and controlling the position of the slide valve Two ty...

Page 29: ...95 35 0 0 100 100 95 30 0 0 100 100 100 0 0 0 Loading sequence Unloading sequence Lead circ Lag circ 1 Lag circ 2 Lead circ Lag circ 1 Lag circ 2 0 0 0 100 100 100 30 0 0 100 100 95 35 0 0 100 100 90...

Page 30: ...he contact is closed the unit enters the ice storage mode Space temperature AI 01 J25 Analogue input Active setpoint reset via space temperature control Capacity limit control AI 10 J9 Analogue input...

Page 31: ...g Full Load Timeout when the water temperature setpoint is not reached Full Load Timeout GEN_CONF General Configuration 7 21 Dry cooler option 30XW 30XW units may come with the dry cooler option that...

Page 32: ...6 holiday periods Each period is defined by three parameters the month the start day and the duration of the holiday period During the holiday periods the controller will be in occupied or unoccupied...

Page 33: ...ight part of the screen and then select Current Alarms 8 4 Resetting alarms Touch Pilot control distinguishes between two types of alarms General alarms are used to indicate pumps failure transducers...

Page 34: ...ove As above As above 24 15026 Economizer gas thermistor fault circuit C As above As above As above 25 15030 Free cooling liquid thermistor fault circuit A As above Free cooling disabled As above 26 1...

Page 35: ...ump is running Discharge pressure transducer defective refrigerant leak or low condenser water temperature 80 10003 Condenser frost protection circuit B As above Circuit B shuts down but the pump is r...

Page 36: ...uit A Manual None Defective or incorrectly wired solenoid valves defective current transformer 132 10088 Slide valve control unverifiable circuit B Manual None As above 133 10089 Slide valve control u...

Page 37: ...temperature and the VFD fan 67 Alarm Option configuration has changed Contact Carrier Service 68 Alarm Emergency stop Contact Carrier Service 71 Alarm PTC 1 emergency stop Contact Carrier Service 72 A...

Page 38: ...rvice 8 Alert DC undervoltage Contact Carrier Service 9 Alert Inverter overloaded Check the VFD output current 10 Alert Motor overtemperature Check the motor temperature 11 Alert Motor thermistor Cont...

Page 39: ...No 13453 07 2016 Supersedes order No 13453 03 2016 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Reviews: