6.4 -
Configuration menu
Icon
Displayed text*
Description
Associated table
General Configuration
General configuration
GEN_CONF
Pump Configuration
Pump configuration
PUMPCONF
User Configuration
User configuration
USERCONF
Reset Configuration
Reset configuration
RESETCFG
Schedule Menu
Schedule menu
SCHEDULE
Holiday Menu
Holiday menu
HOLIDAY
Broadcast Menu
Broadcast menu
BROCASTS
Date/Time Configuration
Date/time configuration
DATETIME
Control Identification
Control identification
CTRL_ID
*Depends on the selected language (English by default).
..GEN_CONF.–.General.configuration
No.
Status
Default
Unit
Displayed text*
Description
1
0 to 2
0
-
Cir Priority Sequence
Circuit priority
2
0=Auto, 1=A Prio
0 = Automatic circuit selection
1 = Circuit A priority
3
2=B Prio
2 = Circuit B priority
4
no/yes
no
-
Staged Loading Sequence
Staged loading sequence
5
no/yes
no
-
Ramp Loading Select
Ramp loading selection
6
1 to 15
1
min
Unit Off to On Delay
Unit Off to On delay
7
00:00
0
-
Night Mode Start Hour
Night mode start time
8
00:00
0
-
Night Mode End Hour
Night mode end time
9
0 to 100
100
%
Night Capacity Limit
Night capacity limit
10
Basic Menu Configuration
Basic menu configuration
11
0 = All Access
0 = All access
12
1 = no alarm menu
1 = No alarm menu
13
2 = no setpoint menu
2 = No setpoint menu
14
3 = 1 + 2
3 = No alarm and no setpoint menu
15
0 to 2
0
-
Demand Limit Type Select
Demand limit selection
16
0 = None
0 = None
17
1 = Switch Control
1 = Switch control
18
2 = 4-20mA Control
2 = 4-20 mA control
19
0 to 20
0
mA
mA For 100% Demand Limit
100% demand Limit (mA)
20
0 to 20
10
mA
mA For 0% Demand Limit
0% demand Limit (mA)
21
no/yes
no
-
Current Limit Select
Current limit selection
22
0 to 4000
2000
A
CurrentLimit at 100%
Current limit at 100%
23
14.4 to 15
10
^C
Free Cooling Delta T Th
Free cooling delta temperature
24
20 to 300
30
min
Full Load Timeout
Full load timeout
25
no/yes
no
-
Ice Mode Enable
Ice mode enabled
26
no/yes
no
-
Reverse Alarms Relay
Reverse alarms relay
*Depends on the selected language (English by default).