..PUMPCONF.–.Pump.configuration
No.
Status
Default
Unit
Displayed text*
Description
1
0 to 4
0
-
Condenser Pumps Sequence
Condenser pumps sequence **
2
0 to 4
0
-
Cooler Pumps Sequence
Evaporator pumps sequence
3
0 = No Pump
0 = No pump
4
1 = One Pump Only
1 = One pump
5
2 = Two Pumps Auto
2 = Two pumps automatic control
6
3 = Pump#1 Manual
3 = Pump 1 manual
7
4 = Pump#2 Manual
4 = Pump 2 manual
8
24 to 3000
48
hour
Pump Auto Rotation Delay
Pump rotation delay
9
no/yes
no
-
Pump Sticking Protection
Pump sticking protection
10
no/yes
no
-
Stop Pump During Standby
Pump stop when the unit is in standby
11
no/yes
yes
-
Flow Checked If Pump Off
Flow check when the pump is off
12
no/yes
no
-
Cooler Pump Off In Heat
Evaporator pump off in Heating
13
no/yes
no
-
Cond Pump Off In Cool
Condenser pump off in Cooling
*Depends on the selected language (English by default).
** Please note that the unit can control only one condenser pump. This value can be set to “0” or “1”.
..USERCONF.–.User.configuration
No.
Status
Default
Unit
Displayed text*
Description
1
1 to 9999
11
-
User Password
User password
*Depends on the selected language (English by default).
..RESETCFG.–.Reset.configuration
No.
Status
Default
Unit
Displayed text*
Description
1
0 to 4
0
-
Cooling Reset Select
Cooling reset selection
2
0 to 4
0
-
Heating Reset Select
Heating reset selection
3
0=None, 1=OAT
0 = None
1 = OAT
4
2=Delta T, 4=Space Temp
2 = Delta T
4 = Space temperature
5
3=4-20mA control
3 = 4-20 mA control
6
Cooling
Cooling
7
-10 to 51.7
-10
°C
OAT No Reset Value
OAT, no reset value
8
-10 to 51.7
-10
°C
OAT Full Reset Value
OAT, max. reset value
9
0 to 13.9
0
^C
Delta T No Reset Value
Delta T, no reset value
10
0 to 13.9
0
^C
Delta T Full Reset Value
Delta T, max. reset value
11
0 to 20
0
mA
Current No Reset Value
Current, no reset value
12
0 to 20
0
mA
Current Full Reset Value
Current, max. reset value
13
-10 to 51.7
-10
°C
Space T No Reset Value
Space temperature, no reset value
14
-10 to 51.7
-10
°C
Space T Full Reset Value
Space temperature, max. reset value
15
-16.7 to 16.7
0
^C
Cooling Reset Deg. Value
Maximum cooling reset value
16
Heating
Heating
17
-10 to 51.7
-10
°C
OAT No Reset Value
OAT, no reset value
18
-10 to 51.7
-10
°C
OAT Full Reset Value
OAT, max. reset value
19
0 to 13.9
0
^C
Delta T No Reset Value
Delta T, no reset value
20
0 to 13.9
0
^C
Delta T Full Reset Value
Delta T, max. reset value
21
0 to 20
0
mA
Current No Reset Value
Current, no reset value
22
0 to 20
0
mA
Current Full Reset Value
Current, max. reset value
23
-10 to 51.7
-10
°C
Space T No Reset Value
Space temperature, no reset value
24
-10 to 51.7
-10
°C
Space T Full Reset Value
Space temperature, max. reset value
25
-16.7 to 16.7
0
^C
Heating Reset Deg. Value
Maximum heating reset value
26
-4 to 32
-17.8
°C
Heating OAT threshold
Heating OAT threshold
27
no/yes
no
-
HSM Both Command Select
HSM both command selection
28
no/yes
no
-
Auto Changeover Select
Automatic changeover selection
*Depends on the selected language (English by default).
..SCHEDULE.–.Schedule.configuration
No.
Name
Displayed text*
Description
1
OCCPC01S
OCCPC01S - Schedule Menu
Unit on/off time schedule
2
OCCPC02S
OCCPC02S - Schedule Menu
Unit setpoint selection time schedule
*Depends on the selected language (English by default).