9
MOLEX
®
MiniFit 538-39-01-2060
4
3
2
1
GND
MOLEX
®
Mini-Fit 538-39-01-2140
G Vbat DI1 S4V S3
S2
S1
G0 GND DI2 S4I Vr1 Vr2 OC
Fig. 2.1
Fig. 2.4
GN
X
RT+
RT
-
PHOENIX
®
MC1,5/3-ST-3,81
Fig. 2.3
2
1
4
3
MOLEX
®
MiniFit 538-39-01-2060
ENGL
ISH
EVD
4
+030220227 - rel. 2.1 - 12.06.2008
Below is a description of the connectors supplied with the EVD00004*0 or purchased in separate
packages (EVD400CON0 for the EVD00004*1). The drawings represent the connectors as seen after
having been fi tted on the EVD
4
.
2.1 Power supply, sensors, digital I/O
The main 14-pin MINIFIT
®
connector is used to connect the main and auxiliary power supply (if the
EVBAT00200/300 module is fi tted), as well as the sensors, digital inputs and transistor output.
This connector accepts wires with cross-section up to 1 mm
2
with MOLEX
®
5556-T barrel.
A kit of pre-crimped 14 x 1 mm
2
cables, length 5 m, is available for purchase (EVDCAB0500).
line
Function
G, G0
24 Vac power supply
GND
Earth for all signals, in electrical contact with GND and the GNX terminal on the main serial
connector
Vbat
Emergency power supply generated by the EVBAT00200 module
DI1, DI2
Digital inputs to be activated by voltage-free contact or transistor to GND, 5 V no-load and 5
mA short-circuited
Vr1, Vr2
5 V references used as power supply to the ratiometric probes
S1
Analogue input for ratiometric probe or NTC low temperature probe
S2
Analogue input for ratiometric probe, NTC high temperature probe or Pt1000
S3
Analogue input for ratiometric probe or NTC low temperature probe
S4I
Analogue input for 4 to 20 mA signal
S4V
Analogue input for 0 to 10 Volt signal
OC
Open-collector transistor output, for up to 100 mA
Table 2.1
For the power supply in particular, observe the diagram shown:
2.2 Main serial port for connection to
tLAN/pLAN/RS485 (supervisor /
Modbus
®
)
Removable terminal for connection to the MASTER unit (µChiller, pCO) or the supervisor (PlantVisor).
line
Function
GNX
Signal earth, in electrical contact with GND on the I/O connector
RT+
+ signal for the RS485 connection (pLAN, supervisor,
Modbus
®
) or DATA signal for the tLAN
connection
RT–
v signal for the RS485 connection (pLAN, supervisor,
Modbus
®
)
Table 2.2
2.3 Stepper motorr
6-pin MINIFIT® connector. Accepts cables up to 1 mm
2
with MOLEX® 5556-T barrel.
Line
Function
GND
Earth electrically connected to GND on the I/O connector, and with the earth connector on the
electrical panel
1
+ Phase A
2
+ Phase B
3
– Phase A
4
– Phase B
Table 2.3
2. INPUTS AND OUTPUTS
G V
bat
DI1 S4V S3 S2 S1
G0 GND DI2 S4I Vr1 Vr2 OC
EVD
4
G B- B+
G0 OUT GND
4 A T
power supply module
EVD
12 V
1,2 Ah
0,8 A T
0,8 A T
24 Vac
230 Vac
optional backup
EVBA
T002
00/3
00
do not connect if EVBAT* is fitted
Fig. 2.2
for code EVD00014**
for code EVD00004**
Summary of Contents for EVD4
Page 1: ...EVD4 Driver for electronic expansion valve User manual...
Page 2: ......
Page 3: ...User manual...
Page 6: ...6...
Page 44: ...44...
Page 47: ......