16
ENGL
ISH
EVD
4
+030220227 - rel. 2.1 - 12.06.2008
INPUT/OUTPUT group
Parameter name
Descriprion
DriverX mode
operating mode of the X-th driver, from pCO
EEV mode man.
enable/disable manual valve positioning
EEV position
calculated electronic expansion valve opening position
Power request
cooling capacity, from pCO
RXXX
refrigerant confi gured for the REFRIGERANT parameter
Superheat
superheat value measured
Saturated temp.
see Ev. probe sat. temp.
Suction temp.
compressor suction temperature value measured
Evaporation probe
Pressure
evaporation pressure value measured
Saturated Temp.
saturated gas temperature value calculated in the evaporator
Condensation
probe
Pressure
condensing pressure value measured, from pCO
Saturated temp
saturated gas temperature value calculated in the condenser, calculated from dry on previous condensing pressure
Aux. probe
value measured by the auxiliary probe set for the AUX. PROBE CONFIG. parameter
Act. SH set
current superheat set point
EVD version H.W
driver hardware version
EVD version S.W
software version installed on the driver
MAINTENANCE group
Parameter name
Description
Manual mng.
driver ‘X’
EEV Mode
electronic expansion valve control mode, read EEV mode man.
Requested steps
required motor position in manual control.
EEV position
calculated electronic expansion valve opening position
Driver ‘X’ status
Go ahead
enable restart following error
Probes offset S1
correction of the lower limit of S1
Probes offset S2
correction of the lower limit of S2
Probes offset S3
correction of the lower limit of S3
ADVANCED SETTINGS – SPECIAL TOOLS
Not available
ALARMS (for driver ‘X’)
Parameter name
Description
alarm probe error
active following an error on the signal from the probe
alarm Eeprom error
active following an EEPROM memory error
alarm MOP timeout
active in conditions with excessive evaporation pressure
alarm LOP timeout
active in conditions with insuffi cient evaporation pressure
alarm Low Superheat
active in low superheat conditions
EEV not closed
active due to failed valve closing
driver X high superheat
driver X with high superheat
3.2.3 Start-up
After having connected the EVD
4
, cas described in 3.4.1, confi gure the parameters listed in 3.4.2 using
the display that manages the pCO, according to the application and/or systems used. For the unit to be
correctly operated, the SYSTEM SET and AUTOSETUP levels need to be compiled.
The SYSTEM SET level must be compiled, as this contains the information on what is physically installed
in the system. Selecting the type of driver and enabling any advanced functions will allow access to
specifi c fi elds/masks in this or other menus.
The AUTO SETUP level of parameters must also be compiled, and contains fundamental information on
the type of unit.
The ADVANCED SET branch is not required for standard superheat control and is provided for expert
users and/or to implement non-standard functions.
If some essential fi elds have not been confi gured, the alarm message
– DRIVER “x” AUTOSETUP PROCEDURE NOT COMPLETED –
will prevent the unit from being started until the autosetup procedure has been completed.