3.3 Application as positioner (EVD000*40* and EVD000*43*)
The EVD
4
code EVD000*40* (or EVD000*43*) can be used as a positioner for electronic expansion
valves, proportional to a 4 to 20 mA or 0 to 10 Volt signal from a controller.
3.3.1 Connections
Communication: connect S4I and GND to the controller for 4 to 20 mA signals;
connect S4V and GND to the controller for 0 to 10 Volt signals (Fig. 3.9).
Confi guration:
connect the converter (CVSTDUTTL0 or CVSTD0TTL0) to the service serial port and to a
PC with USB or RS232 (Fig. 3.10).
Power supply:
with reference to Fig. 3.11, connect G and G0 to the 24 Vac power supply side.
Valve:
with reference to Fig. 3.12 connect the valve according to the type set for the “Valve
type”
parameter.
3.3.2 List of parameters
Below is the list of parameters visible on the EVD4-UI, divided into read and write; the meaning of each
parameter is detailed in APPENDIX II.
Key:
= Main parameters required to start operation;
= Secondary parameters required for optimum operation;
—
= Advanced parameters.
WRITE
Parameter name
Description
Mode dependent parameters (Fig. 9)
Calibr. S4 gain mA
current gain on channel S4
Calibr. S4 offs mA
current offset on channel S4
Calibr. S4 gain Volt
voltage gain on channel S4
Calibr. S4 offs Volt
voltage offset on channel S4
Global parameters (Fig. 9)
Regulation type
type of control
EEV mode man.
enable/disable manual valve positioning
Requested steps
required motor position in manual control
S4 probe type
type of probe on channel S4
Valve type
number that defi nes the type of electronic valve used
KEY 1
KEY 12
En. positioner
enable positioner function
READ
System measurements (Fig. 9)
Parameter name
Description
EEV opening
valve opening as a %
EEV position
position of the valve in steps
S4 signal
signal on input S4
Digital variables (Fig. 9)
Reset to default
confi rm enable default parameters
Functional test
functional test
Digital input 1
status of digital input 1
Stand alone
select stand-alone operation
Key:
A
Service serial port
B
Main serial port
Sporlan
SEI
SEH
CAREL
DANFOSS
ETS
ALCO
EX5/6
2
1
4
3
1
2
3
4
Green
Black
Red
White
Green
Yellow
Brown
White
Green
White
Red
Black
Blue
White
Brown
Black
for code:
EVD00004**
Sporlan
SEI
SEH
CAREL
DANFOSS
ETS
ALCO
EX5/6
2
1
4
3
3
4
1
2
Green
Yellow
Brown
White
Green
Black
Red
White
Green
White
Red
Black
Blue
White
Brown
Black
for code:
EVD00014**
Summary of Contents for EVD4
Page 1: ...EVD4 Driver for electronic expansion valve User manual...
Page 2: ......
Page 3: ...User manual...
Page 6: ...6...
Page 44: ...44...
Page 47: ......