Carel EVD4 User Manual Download Page 20

20

ENGL

ISH

EVD

4

 +030220227 - rel. 2.1 - 12.06.2008 

Custom valve confi guration

Minimum steps

minimum control steps 

Maximum steps

maximum control steps 

Closing steps

steps completed in total closing 

Opening extra steps

enable extra steps in opening 

Closing extra steps

enable extra steps in closing 

Phase current

peak current per phase 

Still current

current with the motor off 

Steprate

motor speed 

Duty cycle

motor duty cycle 

EEV stand-by steps

number of valve standby steps, see standby steps 

S1 probe limits Min

‘zero’ scale for pressure sensor on input S1 

„

S1 probe limits Max

end scale for pressure sensor on input S1 

„

S2-Pt1000 calib.

calibration index for PT1000 sensor 

Alarms delay

Alarms delay Low SH

low superheat alarm delay 

Alarms delay High SH

high superheat temperature alarm delay in CH mode 

Alarms delay LOP

low evaporation pressure (LOP) alarm delay 

Alarms delay MOP

high evaporation pressure (MOP) alarm delay 

Alarms delay probe error

probe error alarm delay 

Stand alone

enable StandAlone 

AUTOSETUP

Parameter name

Description

Re-install AUTOSETUP values

confi rm enable restore parameter default values 

„

 

Circuit/EEV ratio

percentage of the maximum capacity managed by the valve in the circuit where it is installed 

„

Compressor or unit

macroblock parameter that defi nes the integral time 

„

Capacity control

macroblock parameter that defi nes the proportional factor 

„

Evaporator Type

Cool

macroblock parameter that defi nes the integral time 

„

Heat

macroblock parameter that defi nes the integral time 

„

Cool Mode

temperature at minimum operating pressure (MOP) in CH mode 

†

Heat Mode

temperature at minimum operating pressure (LOP) in HP mode 

†

Defr. Mode

temperature at minimum operating pressure (LOP) in DF mode 

†

MOP

Cool Mode

temperature at maximum operating pressure (MOP) in CH mode 

†

Standby steps

temperature at maximum operating pressure (MOP) in HP mode 

†

Defr. Mode

temperature at maximum operating pressure (MOP) in DF mode 

†

High SH alarm threshold

maximum superheat temperature 

ADVANCED SETTINGS – FINE TUNING

Parameter name

Description

CH-Circuit/EEV Ratio

percentage of the maximum capacity managed by the valve in the circuit where it is installed, in CH mode 

CH-Superheat set

superheat set point in CH mode 

cool mode adjust

CH-Proportional gain

PID proportional factor in CH mode 

CH-Integral time

integral time for superheat control in CH mode 

CH-Low Superheat

low superheat value in CH mode 

heat mode adjust

HP-Circuit/EEV Ratio

percentage of the maximum capacity managed by the valve in the circuit where it is installed, in HP mode 

HP-Superheat set

superheat set point in HP mode 

HP-Proportional gain

PID proportional factor in HP mode 

HP-Integral time

integral time for superheat control in HP mode 

HP-Low Superheat

low superheat value in HP mode 

defr. mode adjust

DF-Circuit/EEV Ratio

percentage of the maximum capacity managed by the valve in the circuit where it is installed, in DF mode 

DF-Superheat set

superheat set point in DF mode 

DF-Proportional gain

PID proportional factor in DF mode 

DF-Integral time

integral time for superheat control in DF mode 

DF-Low Superheat

low superheat value in DF mode 

common list adjust

SHeat dead zone

dead zone for PID control

Derivative time

PID derivative time

Low SHeat int. time

integral time for low superheat control

LOP integral time

integral time for low evaporation pressure (LOP) control

MOP integral time

integral time for high evaporation pressure (MOP) control

MOP startup delay

MOP delay time

Hi TCond. protection

maximum condensing temperature

Hi TCond. int. time

integral time for high condensing pressure control (HiTcond)

Dynamic prop. gain

attenuation coeffi cient with change in capacity

Blocked valve check

time after which, in certain conditions, the valve is considered as being blocked

INPUT/OUTPUT group

Parameter name

Descriprion

DriverX mode

operating mode of the X-th driver, from pCO

EEV mode man.

enable/disable manual valve positioning

EEV position

calculated electronic expansion valve opening position

Power request

cooling capacity, from pCO

RXXX

refrigerant confi gured for the REFRIGERANT parameter

Superheat

superheat value measured 

Saturated temp.

see Ev. probe sat. temp.

Suction temp.

compressor suction temperature value measured

Evaporation probe

Pressure

evaporation pressure value measured

Saturated Temp.

saturated gas temperature value calculated in the evaporator 

Condensation 
probe

Pressure

condensing pressure value measured, from pCO

Saturated temp

saturated gas temperature value calculated in the condenser, calculated from dry on previous condensing pressure

Aux. probe

value measured by the auxiliary probe set for the AUX. PROBE CONFIG. parameter

Act. SH set

current superheat set point

EVD version H.W

driver hardware version

EVD version S.W

software version installed on the driver

Summary of Contents for EVD4

Page 1: ...EVD4 Driver for electronic expansion valve User manual...

Page 2: ......

Page 3: ...User manual...

Page 4: ...n at its best for the specific application The lack of such phase of study as indicated in the manual can cause the final product to malfunction of which CAREL can not be held responsible Only qualifi...

Page 5: ...er EVD000 40 and EVD000 43 17 3 4 Application with pCO EVD000041 and EVD000044 via pLAN 19 3 5 Application with supervisor EVD000 42 and EVD000 45 via RS485 22 3 6 Application with Modbus protocoll EV...

Page 6: ...6...

Page 7: ...d step up transformer for backup power supply EVBAT00300 System made up of EVBAT00200 12 V 1 2 Ah battery cable and connectors EVBATBOX10 Metal battery case CVSTDUTTL0 USB converter to connect a PC to...

Page 8: ...troller The converter can power the logical section of the EVD4 but not the expansion valve and therefore this can be configured from the PC without having to connect the instrument to the 24 Vac powe...

Page 9: ...sed as power supply to the ratiometric probes S1 Analogue input for ratiometric probe or NTC low temperature probe S2 Analogue input for ratiometric probe NTC high temperature probe or Pt1000 S3 Analo...

Page 10: ...r cable Fig 2 8 Connect the USB cable to the PC if the EVD4 is not powered by the 24 Vac line it will take its power supply from the serial converter Once the supervisor has been connected start an ap...

Page 11: ...roller with a different communication protocol e g EVD000 40 with pCO via pLAN and is then connected to a unit with the same protocol e g EVD000 40 with pCO or C2 via tLAN the first time that the EVD4...

Page 12: ...ttenuation coefficient with change in capacity SHeat dead zone dead zone for PID control Derivative time PID derivative time Low SHeat int time integral time for low superheat control LOP integral tim...

Page 13: ...tatus LOP status active when in minimum evaporation pressure control status High Tc status active when in high condensing temperature control status alarm Eeprom error active following an EEPROM memor...

Page 14: ...applications In the standard application the EVD4 read and write parameters are organised into three groups accessible from a pCO terminal input output maintenance and manufacturer The SYSTEM SET leve...

Page 15: ...de temperature at minimum operating pressure MOP in CH mode Heat Mode temperature at minimum operating pressure LOP in HP mode Defr Mode temperature at minimum operating pressure LOP in DF mode MOP Co...

Page 16: ...offset S2 correction of the lower limit of S2 Probes offset S3 correction of the lower limit of S3 ADVANCED SETTINGS SPECIAL TOOLS Not available ALARMS for driver X Parameter name Description alarm pr...

Page 17: ...ed to start operation Secondary parameters required for optimum operation Advanced parameters WRITE Parameter name Description Mode dependent parameters Fig 9 Calibr S4 gain mA current gain on channel...

Page 18: ...re described in 3 3 3 as follows Power up the EVD4 from the mains or via converter Connect EVD4 to the PC via the converter Set S4 probe type 5 configuration of input S4 as 4 to 20 mA or 6 0 to 10 V C...

Page 19: ...led in the system Selecting the type of driver and enabling any advanced functions will allow access to specific fields masks in this or other menus The AUTO SETUP level of parameters must also be com...

Page 20: ...tegral time integral time for superheat control in CH mode CH Low Superheat low superheat value in CH mode heat mode adjust HP Circuit EEV Ratio percentage of the maximum capacity managed by the valve...

Page 21: ...om the probe alarm Eeprom error active following an EEPROM memory error alarm MOP timeout active in conditions with excessive evaporation pressure alarm LOP timeout active in conditions with insuffici...

Page 22: ...Prop gain PID proportional factor CH Integral time integral time for superheat control Advanced I SH dead zone dead zone for PID control Derivative time PID derivative time CH Low Superheat low superh...

Page 23: ...cient evaporation pressure EEV not closed active due to failed valve closing Low SH status active when in low superheat control status MOP status active when in maximum evaporation pressure control st...

Page 24: ...erheat control LOP integral time integral time for low evaporation pressure LOP control MOP integral time integral time for high evaporation pressure MOP control Alarms del Low SH low superheat alarm...

Page 25: ...p pendix I Installing and using the EVD4 UI program within the envisaged range Values from 248 to 255 are reserved If set to one of these values or 0 the FW sets the default value without modifying th...

Page 26: ...OGUE R ONLY REGISTER 50 to 86 ANALOGUE R W REGISTER 128 to 150 INTEGER R ONLY REGISTER 163 to 231 INTEGER R W COIL 1 to 20 DIGITAL R ONLY COIL 51 to 84 DIGITAL R W The correspondence between the Carel...

Page 27: ...I R W 8 REGISTER R W 170 I R W 9 REGISTER R W 171 I R W 10 REGISTER R W 172 I R W 11 REGISTER R W 173 I R W 13 REGISTER R W 174 I R W 14 REGISTER R W 175 I R W 16 REGISTER R W 176 I R W 17 REGISTER R...

Page 28: ...OIL R 12 D R 46 COIL R 13 D R 47 COIL R 14 D R 49 COIL R 15 D R 50 COIL R 16 D R 51 COIL R 17 D R 52 COIL R 18 D R 53 COIL R 19 D R 64 COIL R 20 D R W 1 COIL R W 51 D R W 2 COIL R W 52 D R W 3 COIL R...

Page 29: ...uired configuration The interface configuration for the positioner function is shown in Fig 3 21 and is activated by making the EVD4_UI stand alone connection as described in APPENDIX I INSTALLING AND...

Page 30: ...y if the optional EVBAT00200 300 module is installed power supply is guaranteed to the controller for the time required to close the valve Inputs and outputs Analogue inputs input type CAREL code S1 S...

Page 31: ...verage value observed if the swing stops re enable automatic operation and set less reactive parameters decrease the proportional factor increase the integral time Bubbles of air can be seen in the li...

Page 32: ...requires write access to the configuration files Open the IN EVD400UI INI file from the path where EVD4_UI exe is located and make sure that the Paddr parameter is set to 1 Start the EVD4_UI program...

Page 33: ...n Meaningoftheredorgreenrectangle GREEN FALSEorOFFor0orDISABLED inrelationtothemeaningofthereferenceparameter RED TRUEorONor1orENABLED inrelationtothemeaningofthereferenceparameter if the checkbox is...

Page 34: ...essure LOP alarm delay This is the time that passes from when the superheat temperature is continuously less than the value set for LOP cool mode or LOP Defr Mode or LOP Heat Mode to when the user wan...

Page 35: ...arameters and the auxiliary Driver protectors considering the control characteristics of the various types of system 1 Reciprocating 2 Screw 3 Scroll 4 Flooded cabinet 5 Cabinet Cond probe press A 12...

Page 36: ...ment 1 ratiometric pressure 2 NTC 103AT 10000 ohm at 25 C 3 NTC IHS 50000 ohm at 25 C 4 Pt1000 EVD type model of EVD used Model of EVD used from pCO EVD version H W I 100 0 0 0 driver hardware version...

Page 37: ...22 30 30 30 minimum control steps Position below which the valve is considered closed This parameter is only used during repositioning see CH Circuit EEV Ratio MODE I 16 0 0 0 READ ONLY received from...

Page 38: ...ut S1 4 5 V S1 probe limits Min I 41 1 1 1 zero scale for pressure sensor on input S1 Pressure value corresponding to the minimum of ratiometric output S1 0 5 V S2 Pt1000 calib I 68 0 0 0 calibration...

Page 39: ...s not completely closed and attempts to close it by performing Maximum steps 128 steps every second until the SH reaches coherent values The procedure is stopped if the condition persists for Maximum...

Page 40: ...patibility with the chosen refrigerant The following values are recommended as a reference and starting point for the configuration of the EVD400 and the PID control The users can then check whether o...

Page 41: ...dt Ti oppure u t K e t 1 e t dt Td de t dt This means that the control is calculated as the sum of three contributions P or proportional action Ke t k proportional gain I or integral action Ti K e t d...

Page 42: ...is Kp 100 BP In the first diagram in Fig 3 Bp 50 hence Kp 2 while in the second BP 10 and thus Kp 10 The proportional action of the PID controllers is set by the operator as the proportional band cha...

Page 43: ...alue of the derivative time Tp decreases swings however there may be fluctuations around the set point The derivative action makes the control depend on the future of the error that is on the directio...