Section 7. Installation
225
argument
TRUE
is predefined in the CR6 operating system to only equal
-1
, so
only the argument
-1
is
always
translated as
TRUE
. Consider the expression
If
Condition(1) = TRUE
Then
...
This condition is true only when Condition(1) =
-1
. If Condition(1) is any other
non-zero, the condition will not be found true because the constant
TRUE
is
predefined as
-1
in the CR6 system memory. By entering
= TRUE
, a literal
comparison is done. So, to be absolutely certain a function is true, it must be set
to
TRUE
or
-1
.
Note
TRUE
is
-1
so that every bit is set high (-1 is &B11111111 for all
four bytes). This allows the
AND
operation to work correctly. The
AND
operation does an AND boolean function on every bit, so
TRUE AND X
will be non-zero if at least one of the bits in X is non-zero (if X is not zero).
When a variable of data type BOOLEAN is assigned any non-zero
number, the CR6 internally converts it to
-1
.
The CR6 is able to translate the conditions listed in table
Binary Conditions of
TRUE and FALSE
(p. 225)
to binary form (-1 or 0), using the listed instructions and
saving the binary form in the memory location indicated. Table
Logical
Expression Examples
(p. 226)
explains some logical expressions.
Non-Zero = True (Sometimes)
Any argument other than
0
or
-1
will be translated as
TRUE
in some cases and
FALSE
in other cases. While using only
-1
as the numerical representation of
TRUE
is safe, it may not always be the best programming technique. Consider
the expression
If
Condition(1)
then
...
Since
= True
is omitted from the expression,
Condition(1)
is considered true if it
equals any non-zero value.
Binary Conditions of TRUE and FALSE
Condition
CRBasic
Instruction(s) Used
Memory Location of
Binary Result
Time
TimeIntoInterval()
Variable, System
IfTime()
Variable, System
TimeIsBetween()
Variable, System
Control Port Trigger
WaitDigTrig()
System
Communications
VoiceBeg()
System
ComPortIsActive()
Variable
PPPClose()
Variable
Measurement Event
DataEvent()
System
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......