Section 10. Troubleshooting
571
•
A hardware failure, such as memory corruption, occurred.
•
Inserting or removing memory cards will generally do nothing to cause
the CR6 to miss data. These events affect table definitions because they
can affect table size allocations, but they will not create a situation where
data recovery is necessary.
Data can usually be recovered using the
Datalogger Data Recovery
wizard
available in
DevConfig
(p. 148).
Recovery is possible because data in memory is
not usually destroyed, only lost track of. So, the wizard recovers "data" from the
entire memory, whether or not that memory has been written to, or written to
recently.
Once you have run through the recovery procedure, consider the following:
If a CRD: drive (memory card) or a USB: drive (Campbell Scientific mass storage
device) has been removed since the data was originally stored, then the
Datalogger Data Recovery
is run, the memory pointer will likely be in the wrong
location, so the recovered data will be corrupted. If this is the case, put the CRD:
or USB: drive back in place and re-run the
Datalogger Data Recovery
wizard
before restarting the CRBasic program.
In any case, even when the recovery runs properly, the result will be that good
data is recovered mixed with sections of empty or old junk. With the entire data
dump in one file, you can sort through the good and the bad.
10.13 Troubleshooting — Miscellaneous Errors
10.13.1
Voltage Calibration Error!
An input to an analog channel maybe outside ±8 Vdc:
•
Use a volt meter to check between each analog input terminal and a
ground terminal that analog inputs are not greater than ±5 Vdc.
•
Check for condensation which may cause leakage of 12 Vdc into other
regions of CR6 circuitry.
•
Check for a loose ground wire on a sensor powered from 12V.
•
If a volt meter is not available, disconnect any sensor that is powered
from a 12V source to see if the measurements come back to normal. If
multiple sensors are power by 12V, disconnect one at a time.
10.14 Troubleshooting — Rebooting
Following are ways to reboot the CR6. Rebooting should be a last resort.
Regardless of the method used to reboot, try to collect data from the CR6 before
rebooting as there is a good chance data will be lost during the process. If you
can connect using
DevConfig
, try to save CR6 settings.
•
Reboot manually in
terminal mode
(p. 567):
> REBOOT
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......