Section 8. Operation
387
addressing voltage measurement quality:
• Preventing and Attacking Measurement Noise Problems
• Benefits of Input Reversal and Excitation Reversal for Voltage
Measurements
• Voltage Measurement Accuracy, Self- Calibration, and Ratiometric
Measurements
• Estimating Measurement Accuracy for Ratiometric Measurement
Instructions.
The following topics discuss methods of generally improving voltage
measurements. Related information for special case voltage measurements
(thermocouples
(p. 355),
current loops
(p. 380),
resistance
(p. 367),
and strain
(p. 378))
is
located in sections for those measurements.
Single-Ended or Differential?
Deciding whether a differential or single-ended measurement is appropriate is
usually, by far, the most important consideration when addressing voltage
measurement quality. The decision requires trade-offs of accuracy and precision,
noise cancelation, measurement speed, available measurement hardware, and
fiscal constraints.
In broad terms, analog voltage is best measured differentially because these
measurements include noise reduction features, listed below, that are not included
in single-ended measurements.
•
Passive Noise Rejection
o
No voltage reference offset
o
Common-mode noise rejection, which filters capacitively coupled
noise
•
Active Noise Rejection
o
Input reversal
—
Review Input and Excitation Reversal
(p. 350)
for details
—
Increases by twice the input reversal signal integration time
Reasons for using single-ended measurements, however, include:
•
Not enough differential terminals available. Differential measurements
use twice as many H/L terminals as do single-ended measurements.
•
Rapid sampling is required. Single-ended measurement time is about half
that of differential measurement time.
•
Sensor is not designed for differential measurements. Many Campbell
Scientific sensors are not designed for differential measurement, but the
draw backs of a single-ended measurement are usually mitigated by large
programmed excitation and/or sensor output voltages.
Summary of Contents for CR3000 Micrologger
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ......
Page 30: ......
Page 34: ......
Page 36: ......
Page 96: ......
Page 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Page 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Page 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Page 496: ......
Page 502: ......
Page 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Page 566: ......
Page 594: ......
Page 598: ......
Page 600: ......
Page 602: ......
Page 624: ......
Page 642: ......
Page 643: ......