Section 4. Quickstart
48
FIGURE 6: Short Cut Outputs Tab
4.6.4.4 Procedure: (Short Cut Steps 9 to 12)
9. As shown in the right-most pane of the previous figure, two output tables (1
Table1 and 2 Table2 tabs) are initially configured. Both tables have a Store
Every field and a drop-down list from which to select the time units. These
are used to set the time intervals when data are stored.
10. Only one table is needed for this tutorial, so remove Table 2. Click 2 Table2
tab, then click Delete Table.
11. Change the name of the remaining table from Table1 to OneMin, and then
change the Store Every interval to 1 Minutes.
12. Add measurements to the table by selecting BattV under Selected Sensors in
the center pane. Click Average in the center column of buttons. Repeat this
procedure for PTemp_C and Temp_C.
4.6.4.5 Procedure: (Short Cut Steps 13 to 14)
13. Click Finish at the bottom of the Short Cut window to compile the program.
At the prompt, name the program MyTemperature. A summary screen, like
the one in the following figure, will appear showing the pre-compiler results.
Pre-compile errors, if any, are displayed here.
Summary of Contents for CR3000 Micrologger
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ......
Page 30: ......
Page 34: ......
Page 36: ......
Page 96: ......
Page 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Page 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Page 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Page 496: ......
Page 502: ......
Page 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Page 566: ......
Page 594: ......
Page 598: ......
Page 600: ......
Page 602: ......
Page 624: ......
Page 642: ......
Page 643: ......