17
EN
●
Lead the rinsing water hose Ø 8 mm (
13
) to the
sewage system connection (drain) or connect
it to the included BWT siphon and secure the
end to prevent it from flapping about when under
pressure.
● Lead the overflow hose Ø 24 mm (
14
) to a sew-
age system connection (drain) at least 10 cm
lower or connect it to the included BWT siphon
and secure it appropriately.
●
The two hoses connected to the sewage sys-
tem may not be connected or constricted at any
point. When using the BWT siphon, connect it
to the sewage system connection in accordance
with the installation instructions enclosed with
the siphon.
In accordance with EN 1717, the rinsing water and
overflow hoses must be connected to the sewage
system at least 20 mm above the highest possible
waste water level (unimpeded drainage).
● Place the floor sensor on the floor.
6.2
Electrical connections
The following connections are available at the rear
of the Easy Fill technology cover:
15 LAN (RJ45) connection
16 GSM antenna connection (optional, at low
signal strength)
17 Mains cable
18 Fault signal contact connection (3 wire),
potential-free changeover contact (max.
24 V / 0.5 A) Terminal assignment:
Terminal 1-2 closed during operation
Terminal 3-2 closed during fault
> 20 mm
13
14
OUT
IN
16
15
17
18
1 2 3