28
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
priority
is set to heat up the domestic hot
water. When set DHW temperature is
reached, DHW pump stops and CH pump
is activated.
Parallel pumps /shower and
radiator/ symbol appears in upper
part of display. Means that is set
equal priority to both pumps. They work
in parallel and are controlled by
temperature sensors.
Summer mode
/shower and sun/
symbol means than is set Summer
heating mode. Only DHW pump is active.
Burner flame symbol appears in
upper right part of display. Means
that burner is activated. Burner goes into
Ignition mode and upcoming boiler fire
up.
Flame 2 symbol means
Maximum
output mode
of boiler. In this mode
the boiler operates at maximum output.
Flame 1 symbol means
Low output
mode
of boiler. In this mode the
boiler operates at minimum output.
The notice “
Hi
” appearance on the
screen
where
the
boiler
temperature is displayed means
that the measured boiler body
temperature is above 120°C. Flashing and
beeping alarm is activated. When the
issue is corrected, notification can be
deleted. Disconnect fuel auger from boiler
plug-in socket. Upon any such occurrence
please contact immediately your installer
for system checkup.
Boiler increased temperature.
Those two symbols appearance on
the screen where the boiler
temperature is displayed means that
boiler temperature has increased up to
99°C. In such a case, please contact
immediately to your installer to check the
system.
Error symbol
appears in right upper
part of display. Flashing and beeping
error symbol mean error or fault in
boiler operation. Use “
Enter
“ button to
move to next screen with error notification
in lower left part of display. When the
issue is corrected, error notification can
be deleted. When disconnect the boiler
from electrical supply for few seconds and
then switch on it again, boiler goes back
to normal operation (error notification is
deleted).
A
Ash cleaning system is activated.
Factory setting - Alarms
BB ALARM
Reverse fire Alarm (when the
thermostat contact RB input
is open)
SENSOR E1
Boiler Temperature Sensor is
missing (input B)
SENSOR E2
Boiler Temperature Sensor
Short circuit ( input B)
IGNITION
FAIL
Failure ignition
BURNOUT
Exhaust gas temparature
is too low in Operation
mode. If the exhaust gases
temperature drops below
85°C the boiler will shift into
extinguishing mode.
DHW E1
Water Heater Temperature
Sensor is missing (input WH)
DHW E2
Water Heater Temperature
Sensor Short circuit (input
WH)
Cleanup
This alarm appears when gas
temperature rises above
180
о
C
TE Alarm
This alarm appears when
gas temperature rises above
220
о
С
TE E1
Temperature sensor of
exhaust gases is missing