95
büS/CAN open-Design
15.13
Network topology of a büS
/
CANopen system
When installing a büS/CANopen system, ensure that the terminating circuit of the data lines is correct. The
circuit prevents the occurrence of interference caused by signal reflection in the data lines.
The trunk line must be terminated at both ends with 120 Ω resistors and 1/4 W power loss - see
Network topology - büS/CANopen”
.
illustrates a line with one trunk line and several drop lines. Trunk lines and drop lines consist of
identical material.
A unique Node ID (büS/CANopen address) can be allocated to each control head via DIP switches - see
chapter
“15.14 Configuring the Node ID / baud rate”).
Trunk line
büS/CANopen cable
Terminating
resistor
120
Ω
¼ W
Terminating
resistor
120
Ω
¼ W
Drop lines
büS/CANopen
cable,
max. 6 m long
Node 01
Node n
Control head 1 (node 1)
Control head n (node n)
V +
V –
CAN_H
CAN_L
Fig. 43: Network topology - büS/CANopen
15.14
Configuring the Node ID / baud rate
DIP switches for
colour configura
-
tion
DIP switches for
baud rate
8 DIP switches are available for configuration:
• DIP switches 1 to 6 for the Node ID (büS/
CANopen address)
•
DIP switches 7 to 8 for the baud rate
Please note:
Values fixed by DIP switches invalidate software-
configured values!
Fig. 44:
Position of the DIP switches
english
Control Head Type 8681