Important notes for network building:
•
Each gateway
can control up to 63 nodes (Control Heads Type 8681 büS/CANopen) if the network
topology considers the max. permitted cable length and the required power supply.
Each node
requires a
unique “Node ID”,
otherwise an error occurs.
•
The max. total line length
is 200 m for 125 kbit/s, 100 m for 250 kbit/s, 40 m for 500 kbit/s.
•
The max. cable length for a single drop line
is 6 m,
the max. total length of all drop lines
in the
network is 100 m for 125 kbit/s, 55 m for 250 kbit/s, 30 m for 500 kbit/s.
•
If the
voltage drop i
s too large, an
additional power supply
can feed in at a CAN junction box
(PWR IN connection). In this case, connect CAN ONLY to CAN IN using a CAN cable .
This cable (which interconnects the CAN junction boxes at “CAN ONLY” and “CAN IN”) cannot
be used for T-connectors to branch “nodes” because no power is supplied to this cable (compare
example 3 in chapter
“17 Cabling examples (büS/CANopen)” on page
•
Unused or open connections
must be closed with the appropriate protective caps.
• Required
tightening torque
for all plug-in connections (cables, T-pieces, ...) to ensure the required
leak-tightness against moisture:
0.6 Nm + 0.1 Nm.
•
The CAN cable must be
“terminated” at both ends:
connect a terminating resistor
(120 ohms)
to
the end of the CAN cable / T-connector or, if the line ends with a CAN junction box, connect the
terminating resistor to the CAN OUT connection.
•
For service
work and also when reading out CAN data, a
PC with Bürkert Communicator Type 8920
can be connected to any free connection at the CAN junction box or to the CAN ONLY connection.
A büS stick
is necessary to connect the PC to the CAN network.
•
T-connectors
can be used to connect single “nodes” or a PC to read out the CAN data (via
Bürkert Communicator).