93
büS/CAN open-Design
15.12
Electrical installation - büS/CANopen
For the multi-pole connection variants:
No internal cabling work is required for any of the “büS” variants (with multi-pole connection) which makes
installation and start-up on site considerably easier and quicker, reducing the risk of leaks.
The control head features a multi-pole circular plug (M12 x 1, 5-pole, male) to an 80 cm long cable. The
assignment conforms to the büS/CANopen specification.
However, you will require the correspondingly assembled cable sets with the pin assignments described in
the figure below:
Pin 4:
CAN_H
white
Pin 5:
CAN_L
blue
Pin 1:
Drain
(shielding)
Pin 3:
V–
black
Pin 2:
V+
red
View of plug from the
front onto the pins:
Fig. 41: Bus connection
büS/CANopen
with power supply
For the versions with cable glands:
→
Open the housing (compare chapter “8 Opening and Closing the Housing” on page
) so that this
electronic module is visible as shown below (“Fig. 42”).
→
Connect the different wires of the CAN cable to the screw terminals for the bus signal as specified in the table
“Terminal strip configuration”. The configuration conforms to the büS/CANopen specification.
→
The order numbers of the required CAN cables are listed in chapter “16 Accessories for büS devices”
.