56
AS Interface - Design
Connections:
Multi-pole connection version: 1 x M16 x 1.5 cable gland / size19 with multi-pole connection
(M12 plug according to IEC 61076-2-101, 4-pole) for power supply
and signals, cable length approx. 15 cm or approx. 80 cm
1 x M16 x 1.5 cable gland/size19 - connection option for external
initiator (sealed with dummy plug, remove these before use)
Power supply:
29.5 ... 31.6 V DC (according to specification)
21.0 ... 31.6 V DC (according to specification Power24)
Input / proximity switches (external initiator: S4 in):
Power supply:
AS interface voltage present at control head - 10%
Current carrying capacity,
sensor power supply:
max. 30 mA
Short-circuit protection
design:
DC 2- and 3-conductor,
NO or NC (factory setting NO), PNP output
Input current 1 signal:
ISensor > 6.5 mA, limited internally to 10 mA
Input voltage 1 signal:
USensor > 10 V
Input current 0 signal:
ISensor < 4 mA
Input voltage 0 signal:
USensor < 5 V
Inputs (from master perspective) / binary feedback signals:
The recovery of the 3 valve positions reported back in binary format is described in chapter
129.
Outputs (from master perspective) / solenoid valves:
Typ. switching capacity:
0.9 W (per solenoid valve, for 200 ms after switching on)
Typ. continuous output:
0.6 W (per solenoid valve, from 200 ms after switching on)
Watchdog function:
integrated
Output reduction:
via AS interface - electronics integrated
Typ. Pull-in current (per sol. valve): 30 mA or 0.9 W/200 ms (at 30.5 V AS-i voltage)
Typ. Holding current (per sol. valve): 20 mA or 0.6 W
(at 30.5 V AS-i voltage)
Operating mode:
Long-term operation (100% ED)
Valve type:
Type 6524
Central display of the switching statuses:
Power consumption from AS interface
at 30.5 V AS interface voltage: approx. 33 mA or 1 W per illuminated display
Number of representable colours: 2 colours for process valve switching statuses
1 colour for signaling a fault
For "universal colour switching" see chapter
.
Power supply via AS interface bus (without external power supply):
Max. power consumption from AS-i: <160 mA
Power consumption during normal
operation from the AS-i
(after current reduction):
<150 mA
3 valves activated, 1 position reported back by LED display,
no external initiator
Integrated short-circuit protection
english