156
Maintenance, troubleshooting
Fault description
Possible cause of the fault
Troubleshooting
Feedback signal is "lost" in
system operation
Position in the limit range of the
feedback field
“6.8.1 Feedback fields (position
Repeat the Teach procedure
measuring system (Teach procedure)”)
Check the process valve end positions
during operation against the end posi-
tions in non-operative status of the
system.
Check the pressure supply.
Valve output 2/A1 cannot be
switched off with the control
Magnetic manual override is still
activated
Deactivate the manual override -
compare chapter “22.1 Magnetic
Valve outputs cannot be
switched off by the control
Mechanical manual override at
the solenoid valve is still activated
Deactivate the mechanical manual
overrides on the solenoid valves -
compare chapter “22.2 Mechanical
Faults are signaled by
means of device status LED
/ Top LED
Possible causes may vary
depending on the version
Please read the corresponding descrip-
tions of the respective communication
variant in these operating instructions
No or faulty function of the
process valves
No electrical power supply or
communication for the control
head
Check the power supply and the
communication settings (also refer to
detailed descriptions of the respective
versions in these operating instructions)
No or insufficient pneumatic
supply of the control head
Check the pressure supply and ensure
that supply is sufficient
Incorrect function of the
process valves
Confused pneumatic connection
lines
Check the correct pneumatic con-
nection of the control head to the
process valve
(for fluid diagrams see chapter
Fluid diagrams Type 8681 – examples”
and the operating instructions of the
corresponding process valves)
Valves not correctly connected on
electronic module
Check the correct electrical connection
of the solenoid valves - compare e.g.
“Fig. 15: 24 V DC electronic module”