50
120 V AC - Design
11.5
Electrical installation / start-up
DANGER!
Risk of injury due to electric shock (110 ... 130 V AC)!
`
Before reaching into the system (except for the Teach procedure in a non-explosive atmosphere) switch
off the power supply and secure it to prevent restarting!
`
Observe applicable accident prevention and safety regulations for electrical equipment!
`
When setting the position measuring system (Teach procedure), do not contact any live components!
Procedure:
→
Open the housing following the instructions in chapter
“8 Opening and Closing the Housing”
→
Assemble connection cables for signals and power supply as well as for the external initiator where nec-
essary in observance of the rules of technology.
→
Insert cables through the respective cable glands into the interior of the housing.
→
Connect the wires to the connection terminals according to the connection configuration described in
“Fig. 19: 120 V AC electronic module”. If required, secure the cable with a cable clip.
DANGER!
Risk of electric shock if the PE connection is not connected!
`
the PE connection must be connected!
→
Clamp the protective conductor to the PE connection.
→
Check correct grounding.
→
Close the housing following the instructions in chapter
“8 Opening and Closing the Housing”
.
NOTE!
Ensure IP protection!
`
To ensure IP protection, the union nuts of the cable glands must be tightened in accordance with the
cable sizes or dummy plugs used (approx. 1.5 Nm).
`
If no external initiator is used, the right-hand connection opening must be tightly sealed using a dummy
plug or using a cable gland (SW 19, Ø 3 - 6 mm) + dummy plug (Ø 5 - 6 mm)!
NOTE!
Use of the control head in a potentially explosive atmosphere
`
Only use cables and cable glands which are approved for the respective application area and fit the
cable glands according to the respective operating instructions!
`
Close all unnecessary openings with lock screws/plugs approved for explosions area!