71
DeviceNet - Design
The addresses listed in the table “Static input assemblies” can be used as path data for the Produced Con
-
nection Path attribute of an I/O connection.
Nevertheless, by using this address data, the attributes combined in the assemblies can also be accessed
acyclically via Explicit Messages.
13.11.2
Static output assembly
Name
Address of data attribute of the
assemblies for read access.
Class, instance, attributes
Format of the data attribute
Value 0: OFF,
Value 1: ON
Solenoid valves V1…3
4, 21, 3
Byte 0:
Bit 0: Solenoid valve V1
Bit 1: Solenoid valve V2
Bit 2: Solenoid valve V3
Bit 3…7: not used
The address listed in the table “Static output assembly” can be used as path data for the Produced Con
-
nection Path attribute of an I/O connection.
Nevertheless, by using this address data, the attributes combined in the assemblies can also be accessed
acyclically via Explicit Messages.
13.12
Configuration of the device
13.12.1
Configuration of the safety position of solenoid valves during a
bus error
The valve safety position and the safety mode attributes can be used to configure the solenoid valves in the
event of a bus error.
The configuration data of the (behaviour of) solenoid valves in case of a bus error can be accessed acyclically
via Explicit Messages.
• The Get_Attribute_Single service stands for a read access of the configuration data.
• The Set_Attribute_Single service stands for a write access of the configuration data.
1 data byte for safety mode:
(attribute address:
class 150, instance 1, attributes 7)
1 data byte for valve safety position:
(attribute address:
class 150, instance 1, attributes 6)
Bit
Mode
Value assignment
Bit
Solenoid valve
Value assignment
Bit 0
Charac-
teristics in
event of bus
error
0 Approach
safety position
1 Retain last valve
position
Bit 0
Y1 (solenoid valve
V1
)
Value 0: OFF / value 1:
ON
Bit 1
Y2 (solenoid valve
V2
)
Value 0: OFF / value 1:
ON
Bits
1...7
not used
0 (always)
Bit 2
Y3 (solenoid valve V3)
Value 0: OFF / value 1:
ON
Bits
3...7
not used
0 (always)
english
Control Head Type 8681