134
Position Measuring System
Automatic Teach function / Autotune 2:
Control
Effect on the process valve
Internal program
Error
T2 + T3
Autotune mode started
T2
Autotune 2 starts
Open position
Teach
T2
Valve closing
Activate
V1
Wait period
10s
Closed position
Teach
T1
Open valve
Deactivate
V1
Valve opens
Wait on position S2
S2
Timeout 15 s
Autotune mode completed
Automatic Teach function / Autotune 3:
Control
Effect on the process valve
Internal program
Error
T2 + T3
Autotune mode started
T3
Autotune 3 starts
Closed position
Teach
T1
Open valve
Activate
V1
Wait period
10s
Open position
Teach
T2
Valve closing
Deactivate
V1
Valve closes
Wait on position S1
S1
Timeout 15 s
Open clock valve plate
Activate
V2
Wait period
10s
Clock valve plate
Teach
T3
Valve closing
Deactivate
V2
Valve closes
Wait on position S1
S1
Timeout 15 s
Autotune mode completed