79
IO-Link - Design
Inputs (control head –> IO-Link master/PLC) / binary or analogue feedback signals:
The recovery of the valve positions 3 reported back in binary format or the analogue position signal is
described in chapter
“20 Position Measuring System” on page
129. The analogue target position signal
(resolution: 0.1 mm) is available as a cyclic value/ parameter.
Outputs (
IO-Link master/PLC –> Control head
) / solenoid valves:
Typ. switching capacity: 0.9 W (per solenoid valve, for 200 ms after the power has been switched on)
Typ. continuous capacity:
0.6 W (per solenoid valve from 200 ms after the power has been switched on)
Reduction in output:
Integrated via the IO-Link electronics
Typ. inrush current:
38 mA or 0.9 W / 200 ms (per solenoid valve)
Typ. hold current:
25 mA or 0.6 W at 24 V DC (per solenoid valve)
Operation mode:
Continuous operation (100% duty cycle)
Valve types:
6524
Central display of the switching statuses:
Current consumption from IO-Link
at 24 V DC:
Approx 21 mA for a power supply of 24 V DC for each indicator light shown;
for colour switching see chapter
“21 LED Colour Assignments” on page
english