120 V AC - Design
Example 2:
3 valves have been activated simultaneously, one position is reported (persistent state):
P
Total
=
P
El
+ 3 x P
Valve
+ 1 x P
LED
7.0 VA
=
1.2 VA
+ 3 x 1.4 VA
+ 1 x 1.6 VA
or
I
Total
=
I
El
+ 3 x I
Valve
+ 1 x I
LED
59 mA
=
10 mA
+ 3 x 12 mA
+ 1 x 13 mA
When using an external initiator, its power requirement should be added.
11.4
Safety instructions
DANGER!
Risk of injury due to electric shock (110 ... 130 V AC)!
`
Before reaching into the system (except for the Teach procedure in a non-explosive atmosphere) switch
off the power supply and secure it to prevent restarting!
`
Observe applicable accident prevention and safety regulations for electrical equipment!
`
When setting the position measuring system (Teach procedure), do not contact any live components!
Risk of electric shock if the PE connection is not connected!
`
the PE connection must be connected!
Danger of explosion in a potentially explosive atmosphere (only in the event of a fault as zone 2)!
`
Opening the hood or the housing in a potentially explosive atmosphere is only allowed in a not ener-
gised state!
WARNING!
Risk of injury from improper installation!
`
Installation may be carried out by trained technicians only and with the appropriate tools!
Risk of injury from unintentional activation of the system and uncontrolled restart!
`
Secure system against unintentional activation.
`
Following installation, ensure a controlled restart.
english
Control Head Type 8681