xviii
Installation Guide
Protection against Electrostatic Discharges
CMOS (Complementary Metal Oxide Semiconductor) technology is highly sensitive to
electrostatic discharges. The use of conductive antistatic flooring is strongly recommended.
Maintenance personnel must wear wrist-straps before handling electronic equipment.
A ground socket is provided in each cabinet.
Shocks and Vibrations
The servers comply with standards:
IEC 60068-1
IEC 60068-2-6
IEC 60068-2-27
IEC 60068-2-31
IEC 60068-2-47
IEC 60068-2-64
IEC 60050
ISO 2041
ISO 5348
ISO 5344
ISO 8626
Operating Mode (on levelers)
•
Sinusoidal vibrations:
-
Duration: 1 sweep, 1 octave/mn
-
5 - 16 Hz range: 0.25 mm peak
-
16 -200 Hz range: 0.25 g peak
•
Random excitation:
-
Duration: 15 mn
-
Frequency: 5 - 200 Hz
-
Spectral density: 1.5x10
-4
g /Hz
-
Root mean square acceleration: 0.17g RMS
Non-operating Mode (on castors)
•
Sweep sine:
-
Duration: 1 sweep, 1 octave/mn
-
5 - 16 Hz range: 0.25 mm peak
-
16 - 200 Hz range: 0.25 g peak
•
Random excitation:
-
Duration: 15 mn
-
Frequency: 5 - 200 Hz
-
Spectral density: 1.5x10
-3
g /Hz
-
Root mean square acceleration: 0.54g RMS
Shock Tests:
•
Duration: 11 ms
•
Form: 1/2 sinusoidal
•
Amplitude: 15 g
Summary of Contents for NovaScale 5xx5
Page 1: ...NovaScale 5xx5 Installation Guide NOVASCALE REFERENCE 86 A1 40EM 06...
Page 2: ...BLANK...
Page 8: ...vi Installation Guide Index X 1...
Page 12: ...x Installation Guide...
Page 22: ...xx Installation Guide...
Page 26: ...xxiv Installation Guide...
Page 105: ...2 55 Setup Procedure...
Page 116: ...A 10 Installation Guide...
Page 134: ...X 4 Installation Guide...
Page 137: ...BLANK...
Page 138: ...BULL CEDOC 357 AVENUE PATTON B P 20845 49008 ANGERS CEDEX 01 FRANCE 86 A1 40EM 06 REFERENCE...
Page 140: ......