4.8 Damped oscillations
Test carried out according to
EN 61000-4-12
Limits according to
EN 61131-2
Power I/O, L to L
±
1 kV, 1 MHz, repeat rate
400/seconds, length 2 seconds,
connection lengths 2 m, criteria B
Power I/O, L to PE
±
2.5 kV, 1 MHz, repeat rate
400/seconds, length 2 seconds,
connection lengths 2 m, criteria B
Table 132: Test requirements - Damped vibration