Standards and certifications • Requirements for immunity to disturbances
Chap
ter 5
Sta
nda
rds a
nd
certi
fica
tion
s
181
Automation PC 820 User's Manual V 1.00
4.3 High-speed transient electrical disturbances (Burst)
4.4 Surge voltages (Surge)
Test carried out according to
EN 61000-4-4
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
Limits according to
EN 55024
AC power I/O
±
2 kV, Criteria B
-
±
1 kV, Criteria B
AC power inputs
-
±
2 kV, Criteria B
-
AC power outputs
-
±
1 kV, Criteria B
-
DC power I/O >10 m
1)
1) For EN 55024 without length limitation.
±
2 kV, Criteria B
-
±
0.5 kV, Criteria B
DC power inputs >10 m
-
±
2 kV, Criteria B
-
DC power outputs >10 m
-
±
1 kV, Criteria B
-
Functional ground connections,
signal lines and I/Os >3 m
±
1 kV, Criteria B
±
1 kV, Criteria B
±
0.5 kV, Criteria B
Unshielded AC I/O >3 m
-
±
2 kV, Criteria B
-
Analog I/O
±
1 kV, Criteria B
±
1 kV, Criteria B
-
Test carried out according to
EN 61000-4-4
Limits according to
EN 61000-6-2
AC power I/O
±
2 kV, Criteria B
AC power inputs
-
AC power outputs
-
DC power I/O >10 m
±
2 kV, Criteria B
DC power inputs >10 m
-
DC power outputs >10 m
-
Functional ground connections,
signal lines and I/Os >3 m
±
1 kV, Criteria B
Unshielded AC I/O >3 m
-
Analog I/O
±
1 kV, Criteria B
Table 127: Test requirements - High-speed transient electrical disturbances (burst)
Test carried out according to
EN 61000-4-5
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
Limits according to
EN 55024
AC power I/O, L to L
±
1 kV, Criteria B
±
1 kV, Criteria B
±
1 kV, Criteria B
AC power I/O, L to PE
±
2 kV, Criteria B
±
2 kV, Criteria B
±
2 kV, Criteria B
DC power I/O, L+ to L-, >10 m
±
0.5 kV, Criteria B
-
-
DC power I/O, L to PE, >10 m
±
0.5 kV, Criteria B
-
±
0.5 kV, Criteria B
DC power inputs, L+ to L-
-
±
0.5 kV, Criteria B
-
DC power inputs, L to PE
-
±
1 kV, Criteria B
-
DC power outputs, L+ to L-
-
±
0.5 kV, Criteria B
-
Table 128: Test requirements - Surge voltages
Summary of Contents for Automation PC 820
Page 2: ...2 Automation PC 820 User s Manual V 1 00...
Page 4: ...4 Automation PC 820 User s Manual V 1 00...
Page 6: ...6 Automation PC 820 User s Manual V 1 00...
Page 212: ...212 Commissioning USB flash drive Automation PC 820 User s Manual V 1 00...
Page 246: ...Model number index 246 Automation PC 820 User s Manual V 1 00...