182
Standards and certifications • Requirements for immunity to disturbances
Automation PC 820 User's Manual V 1.00
4.5 Conducted disturbances
DC power outputs, L to PE
-
±
0.5 kV, Criteria B
-
Signal connections >30 m
±
1 kV, Criteria B
±
1 kV, Criteria B
±
1 kV, Criteria B
All shielded cables
-
±
1 kV, Criteria B
-
Test carried out according to
EN 61000-4-5
Limits according to
EN 61800-3
AC power I/O, L to L
-
AC power I/O, L to PE
-
DC power I/O, L+ to L-, >10 m
±
1 kV, Criteria B
DC power I/O, L to PE, >10 m
±
2 kV, Criteria B
DC power inputs, L+ to L-
-
DC power inputs, L to PE
-
DC power outputs, L+ to L-
-
DC power outputs, L to PE
-
Signal connections >30 m
-
All shielded cables
-
Test carried out according to
EN 61000-4-6
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
Limits according to
EN 55024
AC power I/O
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
criteria A
DC power I/O
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
criteria A
Functional ground connections
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
-
Signal connections >3 m
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
criteria A
Test carried out according to
EN 61000-4-6
Limits according to
EN 61800-3
AC power I/O
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
criteria A
Test carried out according to
EN 61000-4-6
Limits according to
EN 61800-3
DC power I/O
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
criteria A
Table 129: Test requirements - Conducted disturbances
Test carried out according to
EN 61000-4-5
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
Limits according to
EN 55024
Table 128: Test requirements - Surge voltages (cont.)
Summary of Contents for Automation PC 820