About this product
Bosch Rexroth AG
, VT-VPCD, RE 30028-B/09.13
The signs +/- light up together with the value shown on the display (positive or
negative).
In conjunction with the 4 keys, the display serves to display and change parameters
and is used for diagnostic purposes. The VT-VPCD can be accessed via a menu
structure. The parameter values can be displayed and changed. Moreover, error
messages are shown on the display.
Software is configured via the serial interface. The graphic below shows the pinout
of the D-SUB socket on the front panel.
Fig. 10: Pinout of the D-SUB socket RS232
The connection for Profibus communication is made using a 9-pin D-SUB socket on
the front panel (optional). The graphic below shows the pinout of the D-SUB socket
for Profibus.
Fig. 11: Pinout of Profibus D-SUB socket
Fig. 12: Address setting for Profibus
Sign of display value
Display
Serial interface
1
6
9
GND
5
Send data (RS232)
Receive data (RS232)
Profibus interface
(optional)
GND
RxD/TxD-N (A-line)
RxD/TxD-P (B-line)
VP (5 V)
↑
ON
1 2 3 4 5 6 7 8
LSB
MSB
1 2 4 8 16 32 64
↓
OFF
Not used, must be “OFF“