48/60 Operation
Bosch Rexroth AG
, VT-VPCD, RE 30028-B/09.13
The control electronics is in the configuration mode “EDIT Parameters”.
How to change from the operation mode to the configuration mode:
Precondition: You are in the operation mode.
The display shows as running text the manufacturer’s name and the version number
of the control electronics or a text determined individually by you.
▶
Press the control keys “ENT” and “ESC” simultaneously (exception: for “EDIT
Parameters“, see above) and hold them down (for at least 2 seconds) until
“Setup” is shown on the display of the control electronics.
The control electronics is now in the setup mode.
How to exit the configuration mode:
In the present example, the second level of the menu tree “Setup” was selected.
The display of the control electronics shows “Sprache/Language” as running text.
▶
Press the “ESC” control key.
The display shows “Setup” as running text.
▶
Press the control key “ESC”.
The display shows as running text the manufacturer’s name and the version
number of the control electronics or a text determined individually by you.
If no entry is made within a minute in the configuration mode, the control
electronics automatically changes to the next higher level until the operation
mode is reached.
The control electronics VT-VPCD is fully operable in the configuration mode.
How to change a parameter with the help of the control keys:
CAUTION!
Uncontrolled system behavior! When parameters are changed with the
help of the control keys of the control electronics, the entries are not checked for
the signal “enable active”.
▶
Do not change one or several analog inputs from voltage to current or from
current to voltage. When you change the type of one or several analog inputs, the
active value is not interpreted as desired.