Move to Area
Default:
P
Selection:
Blank, E, or P
Function No.
Function Name
Alternate Keystroke
30
Move to Area
[COMMAND][5][0]
Use this function to switch the keypad’s assignment
temporarily to a different area. This command can be
used to perform any function that can be performed
by a keypad assigned to the area in programming.
Users are limited to performing functions enabled by
the authority level they have in the area to which the
keypad is moved. After 15 seconds of no activity at the
keypad, the keypad reverts back to the originally
programmed area.
Display Rev
Default:
E
Selection:
Blank, E, or P
Function No.
Function Name
Alternate Keystroke
32 Display
Software
Revision
[COMMAND][5][9]
Use this function to show the control panel’s software
revision number in the keypad display.
Service Walk
Default:
P
Selection:
Blank, E, or P
Function No.
Function Name
Alternate Keystroke
33 Service
Walk
Test
(Menu function only)
Use this function to Walk Test all 246 points in the
entire control panel regardless of the
P## Type
.
The Service Walk Test is available on the
D9412GV2 using the Service Menu
[9][9][ENT]. The D7412GV2
does not
include the Service Walk Test in the
Service Menu. In the D7412GV2, the
Service Walk Test function must be
enabled in the Function List to access the
Service Walk Test.
Default Text
Default:
P
Selection:
Blank, E, or P
Function No.
Function Name
Alternate Keystroke
34 Default
Text
[COMMAND][5][7]
Determining the armed state of an area using the
programmed custom text might be difficult. Use this
function to switch temporarily to the control panel
default text, shown on the program record sheet.
Change Skeds
Default:
P
Selection:
Blank, E, or P
Function No.
Function Name
Alternate Keystroke
35 Change
Skeds
[COMMAND][5][2]
Execute this panel-wide function from any keypad
assigned to an area where the user has authority. Use
this function to change the
S## Time
from the keypad
to make adjustments to Skeds.
#36 Invisible Walk Test
Default:
P
Selection:
Blank, E, or P
This function allows a user with the
L## Invisible
Walk Test
authority to test invisible interior or
perimeter controlled points that are within the scope of
the keypad, without sending reports to the central
station. Invisible points must have the
P## Invisible
Pt
function programmed
Yes
.