Relay functions that must be reset manually
with Change Relay function (COMMAND 54):
Fail To Close
Force Armed
Duress Log
%
Full
2.13.1 Area
Relays
Each area can be assigned a unique relay number for
each of the events listed in this section.
Area
Default:
1
Selection:
1 to 8
Enter the area number you are programming.
A# Alarm Bell
Default:
A
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
This voltage output relay activates and provides
12 VDC output when a Non-fire point (
P## Fire
is
No
) assigned to this area activates an alarm.
Burg Time and Burg Pat must be
programmed in Bell Parameters. This relay
activates according to the bell pattern and
remains active until the bell time expires.
P## Silent Bell
must be
No
for the bell to
ring upon alarm.
A# Fire Bell
Default:
A
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
This voltage output relay activates and provides
12 VDC output when a Fire point (
P## Fire
is
Yes
)
assigned to this area activates an alarm.
Fire Time and Fire Pat must be
programmed in Bell Parameters. This relay
activates according to the bell pattern and
remains active until the bell time expires.
P## Silent Bell
must be
No
in order for the
bell to ring upon alarm.
Although Relay C is a valid entry for
A#
Fire Bell
, do not program Relay C for this
entry. Use Relay A for the
A# Fire Bell
.
A# Reset Sensors
Default:
C
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Unlike the default relay for Alarm Bell and Fire Bell,
this voltage-output relay (Relay C) de-activates for 5
seconds when the
Reset Sensors?
function is
activated from the keypad or during a Fire Walk Test.
The Reset Sensors time converts from the
5 second default time to the time
programmed in
A# Verify Time
(
Section
2.9 Area Parameters
on page
5
) when a
point programmed for
P## Alarm Verify
(
Section 4.1 Point Index
on page 81)
enters an alarm condition.
When sharing one relay to reset sensors in
two or more areas, you must program the
following. Failure to do so causes
TROUBLE PT ### for all point types
programmed as
P## Resettable
.
•
CC # Scope
must include all areas that
share the relay.
•
L## Reset Sensors
authority must be
assigned to the pass code that
activates the COMMAND 47 or Reset
Sensor function.
•
A# Verify Time
must be the same
number of seconds for all areas that
share the relay.
A# Fail to Close
Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
This relay activates when the Closing Window expires
for the specified area. It remains active until midnight,
another Closing Window starts, or the control panel
resets, whichever occurs first. Refer to number 5 in
Programming Tips
on page 74 for addition relay
functions.