D9412GV2/D7412GV2 |
Program Entry Guide | 4.0
RADXPNTS
EN
| 87
Bosch Security Systems | 5/05 | F001U003636B
P## Entry Delay
Default:
Refer to the program record sheet
Selection:
5 seconds to 600 seconds
Use this option to enter the amount of entry delay time
that a user has after faulting a Controlled point (
P##
Type 1, 2, 3
) with a delayed response (D) (
P## Pt
Response
) of 4, 5, 6, 7, or 8.
DISARM NOW
appears for
the duration of the time programmed when the point
is faulted in the delay condition.
The D1255 alternates between
DISARM
NOW
and the point text of the point that
caused the area to enter into entry delay.
If this time expires before disarming, or if the point is
faulted to an instant response (I), an alarm occurs.
Make entries in 5 second increments. The
programmer does not allow off-increment
entries.
If another Perimeter or Interior Follower
Delay point trips while the area is already in
entry delay, the control panel adjusts the
delay time to the Delay point with the least
amount of delay time.
When a user enters an area, a Perimeter
point is faulted and the entry delay starts. If
an interior point must fault during entry
delay to allow the user to disarm the area at
a keypad, program
P## Type
as 3 (Interior
Follower).
P## Ent Tone Off
Default:
No
Selection:
Yes or No
Yes
Defeat the entry delay tone when this
perimeter point is faulted.
This is intended for use with points
set to
P## Type 1
(Perimeter).
No
A tone sounds at keypads when this
point starts entry delay.
This option enables and disables the entry delay
warning tone for this point.
Do not set points to
No
if they are actually
used to notify the user to disarm the system.
The possibility of false alarms increases if
the entry delay warning is not used.
Entry Tone can also be turned off when
programming your CC Entry Tone, in
Section 2.10 Keypad
(Command Center)
on page 45, that allows you to manage the
tone by keypad.
You might want to disable the entry tone in
high security applications where you do not
want to annunciate entry delay.
P## Silent Bell
Default:
No
Selection:
Yes or No
Yes
Activate the Silent Alarm relay when
this point enters into alarm. Keypads
do not sound the alarm tone for Non-
fire points.
No
Activate either the Fire Bell relay or
Alarm Bell relay and sound the alarm
tone at keypads when this point
enters into alarm. If this is a Fire
point, it activates the Fire Bell relay
programmed in Relay Parameters.
Otherwise, it activates the Alarm Bell
relay. The amount of time and
pattern of the relay activation is
programmed by area in Bell
Parameters.
If you want this point to ring the bell
because the message failed to reach the
central station receiver, program
P##
Audible After 2 Failures
as
Yes
.
P## Ring Til Rst
Default:
No
Selection:
Yes or No
Yes
The relay programmed to provide
fire alarm output for this point cannot
be de-activated until the point
restores to normal.
No
The relay programmed to provide
fire alarm output for this point can be
de-activated before the point restores
to normal.
Use this option to determine if the bell continues to
ring until the Fire Bell time expires. The point returns
to a normal condition when the user acknowledges the
alarm to silence the bell.