Central Processing Unit
5–20
1070 072 145-102 (01.07) GB
Transmission protocol
The following transmission protocol is permanently set:
D
Even parity
D
1 Stop bit
D
8 Data bits
There are no control lines.
V.24 interface
As the V.24 interface is not electrically isolated from logic circuits and power
supply, this may on rare occasions connectivity problems with devices
whose interface also lacks electrical isolation.
If this is the case, sufficient potential equalization must be established bet-
ween the reference conductors of both interfaces. Only a small potential dif-
ferential may exist between transmitter and receiver, for example:
–2 V < U
diff
< +2 V.
Signal level:
logic 1
–5 V
logic 0
+5 V
Pin assignment, female DB-25 connector:
Pin
Signal designation
Signal function
Housing
Screen
Screening
2
TxD
PLC transmit data
3
RxD
PLC receive data
7
GND
Reference conductor, Ground
20 mA interface
Line status:
logic 1 : 20 mA
logic 0 : no current
Pin assignment, female DB-25 connector (passive):
Pin
Signal designation
Signal function
Housing
Screen
Screening
21
12 V GND
12 V reference conductor
22
RXD+
Receive data +
12
RXD–
Receive data –
23
TXD+
Transmit data +
13
TXD–
Transmit data –
Summary of Contents for CL200
Page 3: ...Antriebs und Steuerungstechnik CL200 Manual CL200 102 Edition ...
Page 8: ...Contents VIII 1070 072 145 102 01 07 GB Notes ...
Page 24: ...System Introduction 2 8 1070 072 145 102 01 07 GB Notes ...
Page 38: ...Module Racks 3 14 1070 072 145 102 01 07 GB Notes ...
Page 82: ...E 24 V Digital Input Modules 6 6 1070 072 145 102 01 07 GB Notes ...
Page 104: ...Digital Input Output Modules 8 10 1070 072 145 102 01 07 GB Notes ...
Page 110: ...DP EA4 Peripheral Bus Station Module 9 6 1070 072 145 102 01 07 GB Notizen ...
Page 114: ...AG S Expansion Module 10 4 1070 072 145 102 01 07 GB Notizen ...
Page 122: ...R200 R200P COM2 E Communication Modules 11 8 1070 072 145 102 01 07 GB Notizen ...
Page 158: ...Appendix A 4 1070 072 145 102 01 07 GB Notes ...