Central Processing Unit
5–16
1070 072 145-102 (01.07) GB
Specifications
Analog inputs
Analog inputs,
as per EN 61131-2
4 power inputs
Input voltage range
D
0 to 10 V, unipolar
D
Selectable between 2 and 10 V
Input resistance
20 k
W
Protective circuit
RC circuit, Schottky diodes
Max. permissible continuous overload
Reverse polarity up to supply voltage
Isolation potential
No isolation
Input filter characteristic
1st order
Conversion time
Cycle time plus 10 ms
Sampling interval
20
m
s
Scanning repeat time
10 ms
Operating mode
Time controlled in 10 ms intervals
Conversion mode
Gradual approximation
Digital display
16 bit, straight binary
Resolution
10 bit
Value of LSB
w/o standardization:
10 V : 2
10
= 9.8 mV
w/ standardization
8 V : 2
10
= 7.8 mV
Temperature coefficient
1%, 5 to 55
_
C
Max. short–term deviation during
pulse shaped interferences
v
2 %
Cable length
max. 100 m, screened
The data related to the analog inputs are stored in the system area, S64
through S71. With standardization enabled, the analog inputs are monitored
for cable breaks. Cable breaks are reported in system area S80.
System area
Analog inputs
S64 / S65
Channel 0
S66 / S67
Channel 1
S68 / S69
Channel 2
S70 / S71
Channel 3
S80
Cable break messages
Summary of Contents for CL200
Page 3: ...Antriebs und Steuerungstechnik CL200 Manual CL200 102 Edition ...
Page 8: ...Contents VIII 1070 072 145 102 01 07 GB Notes ...
Page 24: ...System Introduction 2 8 1070 072 145 102 01 07 GB Notes ...
Page 38: ...Module Racks 3 14 1070 072 145 102 01 07 GB Notes ...
Page 82: ...E 24 V Digital Input Modules 6 6 1070 072 145 102 01 07 GB Notes ...
Page 104: ...Digital Input Output Modules 8 10 1070 072 145 102 01 07 GB Notes ...
Page 110: ...DP EA4 Peripheral Bus Station Module 9 6 1070 072 145 102 01 07 GB Notizen ...
Page 114: ...AG S Expansion Module 10 4 1070 072 145 102 01 07 GB Notizen ...
Page 122: ...R200 R200P COM2 E Communication Modules 11 8 1070 072 145 102 01 07 GB Notizen ...
Page 158: ...Appendix A 4 1070 072 145 102 01 07 GB Notes ...