Central Processing Unit
5–2
1070 072 145-102 (01.07) GB
Unit functions
D
Decoding and processing instructions and commands contained in the
PLC program
D
Memory management for data received from peripherals
D
Detection and processing of interrupt signals
D
System monitoring
PLC program memory
To facilitate PLC program storage, the central processing units feature two
internal memory areas.
D
128 kB of internal RAM
D
128 kB Flash-EPROM memory
With a memory backup battery installed in the NT200 power supply mo-
dule, the PLC program can be processed from within the internal 128 kB
RAM.
When operating without backup battery, the PLC program is processed
from within the 128 kB Flash-EPROM memory.
Also possible is mixed operation using both RAM and Flash-EPROM me-
mory for data storage.
When operating with RAM or Flash-EPROM, the following memory capaci-
ties are available to store the application program:
D
12 kB instructions plus 16 kB data modules, OR
D
18 k instructions without data modules
These values are doubled in mixed operation.
The selection of RAM and Flash-EPROM memory and the definition of
mixed operation is accomplished with the use of the PLC utility program. Re-
fer also to order no. for “CL200 Operations List”, in section 1.6.
Functional features
D
Cyclical program processing w/ OM1 organization module
D
Setting system parameters in OM2 organization module
D
Controlling program processing via organization module OM5 or OM7
D
Error management in OM9 organization module
D
2 organization modules for timer controlled functions
D
3 organization modules for interrupt inputs
D
Fixation of inputs/outputs and markers
The instruction set used with the CL200 is upward compatible for use with
the CL400 and CL500 controllers.
ZE200, ZE200A, ZE200M, ZE200AM, ZE201, ZE200-DP, ZE200A-DP
Seven variants of the central processing unit are available to ensure optimi-
zed and cost effective adaptation of the CL200 to a variety of tasks:
D
ZE200
System clock, high-speed counters, interrupt inputs
D
ZE200A
System clock, high-speed counters, interrupt inputs, 4 analog inputs, 1
analog output
Summary of Contents for CL200
Page 3: ...Antriebs und Steuerungstechnik CL200 Manual CL200 102 Edition ...
Page 8: ...Contents VIII 1070 072 145 102 01 07 GB Notes ...
Page 24: ...System Introduction 2 8 1070 072 145 102 01 07 GB Notes ...
Page 38: ...Module Racks 3 14 1070 072 145 102 01 07 GB Notes ...
Page 82: ...E 24 V Digital Input Modules 6 6 1070 072 145 102 01 07 GB Notes ...
Page 104: ...Digital Input Output Modules 8 10 1070 072 145 102 01 07 GB Notes ...
Page 110: ...DP EA4 Peripheral Bus Station Module 9 6 1070 072 145 102 01 07 GB Notizen ...
Page 114: ...AG S Expansion Module 10 4 1070 072 145 102 01 07 GB Notizen ...
Page 122: ...R200 R200P COM2 E Communication Modules 11 8 1070 072 145 102 01 07 GB Notizen ...
Page 158: ...Appendix A 4 1070 072 145 102 01 07 GB Notes ...