RM2-DP12 Module
16–2
1070 072 145-102 (01.07) GB
The module uses single modular width.
16.2
Connecting to PROFIBUS-DP
The RM2-DP is connected to the PROFIBUS by means of a male DB-9 con-
nector which, for security reasons, should be screwed tightly onto the female
DB-9 connector of the RM2-DP12. The X71 PROFIBUS connector is located
on the front panel. The pin assignment corresponds to the PROFIBUS stan-
dard.
Pin assignment, female DB-9 PROFIBUS-DP connector:
Pin
Signal
Function
1
–
not used
2
–
not used
3
B_TLG
RX / TX data P
4
RTS_SIG
Repeater control signal P
(TTL signal)
5
GND_ISO
Data reference potential
6
P5V_ISO
E
-pos.
; 100 mA
7
–
not used
8
A_LTG
RX / TX data N
9
GND_ISO
Repeater control signal N
(DGND)
From the P5V_ISO on the X71 PROFIBUS-DP connector, up to 100 mA of
current can be picked off externally.
Baud Rate
The module automatically adjusts to the baud rate of the PROFIBUS-DP
(9600 baud to 12 Mbaud).
Summary of Contents for CL200
Page 3: ...Antriebs und Steuerungstechnik CL200 Manual CL200 102 Edition ...
Page 8: ...Contents VIII 1070 072 145 102 01 07 GB Notes ...
Page 24: ...System Introduction 2 8 1070 072 145 102 01 07 GB Notes ...
Page 38: ...Module Racks 3 14 1070 072 145 102 01 07 GB Notes ...
Page 82: ...E 24 V Digital Input Modules 6 6 1070 072 145 102 01 07 GB Notes ...
Page 104: ...Digital Input Output Modules 8 10 1070 072 145 102 01 07 GB Notes ...
Page 110: ...DP EA4 Peripheral Bus Station Module 9 6 1070 072 145 102 01 07 GB Notizen ...
Page 114: ...AG S Expansion Module 10 4 1070 072 145 102 01 07 GB Notizen ...
Page 122: ...R200 R200P COM2 E Communication Modules 11 8 1070 072 145 102 01 07 GB Notizen ...
Page 158: ...Appendix A 4 1070 072 145 102 01 07 GB Notes ...