Central Processing Unit
5–19
1070 072 145-102 (01.07) GB
5.4.4
X31 Interface for PG Programming Unit
The X31 is a combination V.24 / 20 mA interface in accordance with VDI Gui-
deline VDI 2880, Page 2.
The X31 female DB-25 connector accepts the PG programming unit or an-
other peripheral device, such as the BT20 control panel, for example.
X31 PG program-
ming unit interface
The transmission protocol used on this interface is the BUEP19E (PST).
Baud rate
The baud rate for the X31 programming unit interface is selected with the use
of the S1 DIP switch onboard the central processing unit.
S1 DIP switch
4
3
2
1
OFF
ON
CAUTION
Do not insert or remove the module while the controller is switched
ON! This may destroy the module. Prior to inserting or removing the
module, ensure that module is not energized!
Baud rate [Baud]
S1/1
S1/2
57600
ON
ON
38400
OFF
ON
19200
ON
OFF
9600
OFF
OFF
Switch segments S1/3 and S1/4 are not being used at this time, and shall
therefore be set to OFF.
Summary of Contents for CL200
Page 3: ...Antriebs und Steuerungstechnik CL200 Manual CL200 102 Edition ...
Page 8: ...Contents VIII 1070 072 145 102 01 07 GB Notes ...
Page 24: ...System Introduction 2 8 1070 072 145 102 01 07 GB Notes ...
Page 38: ...Module Racks 3 14 1070 072 145 102 01 07 GB Notes ...
Page 82: ...E 24 V Digital Input Modules 6 6 1070 072 145 102 01 07 GB Notes ...
Page 104: ...Digital Input Output Modules 8 10 1070 072 145 102 01 07 GB Notes ...
Page 110: ...DP EA4 Peripheral Bus Station Module 9 6 1070 072 145 102 01 07 GB Notizen ...
Page 114: ...AG S Expansion Module 10 4 1070 072 145 102 01 07 GB Notizen ...
Page 122: ...R200 R200P COM2 E Communication Modules 11 8 1070 072 145 102 01 07 GB Notizen ...
Page 158: ...Appendix A 4 1070 072 145 102 01 07 GB Notes ...