ACS 653, ACS 663 Service Manual
SP00D00624
2021-04-08
Robert Bosch GmbH
52
Diagnostics and Testing
Will Not Deep Recover
Vacuum Pump Running
1. Verify no issue on ISV recovery way
(one way valve in tank vapor side).
2. Verify the ISV contains a minimum of 454 g
(1 lb) of chargeable refrigerant.
3. Verify the vacuum (S9), deep recover (S12),
and oil return (S13) solenoids are receiving
power and opening properly.
• If not receiving power, check the continuity
of the wiring between solenoid and power
board. Repair as needed.
• If the wiring is correct and no power is
being applied to the solenoid, replace the
power board.
• Verify the accumulator transducer
is functioning properly and reading
accurately.
• Verify the solenoid coil is opening the
solenoid properly.
NOTE:
The oil return (S13) solenoid is controlled
to maintain 0 to 0.2 bar (3 psi) in the accumulator.
Only this solenoid will be activated at a time and
it will be pulsed intermittently.
4. Test the pump per the test procedure in the
Vacuum Pump
section. If it fails, replace
the pump.
Vacuum Pump Not Running
1. Check for proper power source, circuit
breaker, and electrical connectors for
damage or corrosion. Replace or repair as
required.
2. Connect the unit power cable directly to
the power source. Do not use an extension
cord.
3. Check for 230 V at the vacuum pump
connector, pins 2 and 3.
• If voltage is present, replace vacuum
pump assembly.
•
If voltage is not present, continue to next
step.
NOTE:
When checking voltage to the vacuum
pump, it is normal to read low voltage at the
connector when it’s disconnected and the power
to the vacuum pump is off.
4. Check for 230 V from the power board on
connector P6.
NOTE:
If the fan is operating, power is present
at the power board. The fan, vacuum pump,
and compressor use the same power source.
The fan shall operate whenever the power
switch is turned on.
5. Perform functional check.
Fails Service Vacuum
To test the ISV pressure transducer if SERVICE
VACUUM process (end user install) is failed.
To verify ISV pressure transducer, perform the
following:
• Open service menu and go into
Output
test
to enable the tank liquid
solenoid S22, high-side charge solenoid
S6 and low-side charge solenoid S7.
• Compare the ISV pressure with low side
pressure transducer value:
Service
menu
"
Input test
or in the tool bar
(enable “display title info” in maintenance
menu).