FIRE AND ALARM CONSOLE
44
Type alarm loop number or select value by keys ‘
4
’, ‘
3
’ key
and press ‘ENT’.
If the command was successfully comleted ADC or measured
value is displayed in format:
‘
v
device address / loop number: value’. In this example the
measured by ADC value of loop
№
17 of device with address 2
is equal to 51. Each 0,5 seconds console automatically refreshes
given loop ADC value. By means of buttons ‘
4
‘, ‘
3
‘other loop
ADC values of given device can be viewed.
The following tables contain couples of loop resistance and corresponding ADC value.
ADC value can vary from 0 to 255. Value 0 corresponds to loop open circuit, value 255
corresponds to to short circuit.
а
) Correspondence between loop resistance and ‘Signal-20P’ device ADC value:
alarm loop resistance
0
2,0 kOhm 4,7 kOhm 6,0 kOhm
Open
ADC
value
255 89 46 38 0
Normal range for fire loop (type 1, 2, 3) and for alarm loop with tamper checking (type 5)
is from 2,0 kOhm to 6,0 kOhm.
Normal range for alarm loop (type 4) is from 2,0 kOhm to 11,0 kOhm.
б
) Correspondence between loop resistance and ‘S2000-4’ ADC device value:
alarm loop resistance
0
1
kOhm
2
kOhm
4,7
kOhm
6
kOhm
10
kOhm
16
kOhm
Open
ADC value for
S2000-4
255 140
93
49
40
25
16
0
ADC value for
S2000-4-01
255
229
153
81
66
42
27
0
This table can be found in maintenance guide of ‘S2000-4’ device.
Normal range for fire and alarm loops is from 2,0 kOhm to 6,0 kOhm.
В
) Correspondence between alarm loop resistance and ‘Signal-20’ device ver 1.60, 1.61
and below ADC value:
alarm loop Resistance
0
2,0 kOhm
8,2 kOhm
11,0 kOhm
Open
ADC value
255 159 51 39 0
Normal range is from 2,0 kOhm to 11,0 kOhm.
д
) Correspondence between loop resistance and ‘Signal-20’ device series 2 ADC value:
alarm loop Resistance
0
2,0
kOhm
4,7
kOhm
6,0
kOhm
Open
ADC
value
255 89 46 38 0
2.2.3.7
Console date and time setting
Time setting
Type password.
Select ‘AUX FUNCTIONS’ menu item by ‘
4
’, ‘
3
’ and ‘ENT’
keys, or press hot key ‘6’.
Select ‘SET TIME’ menu item by ‘
4
’, ‘
3
’ and ‘ENT’ keys, or
press hot key ‘1’.
v
002/017:
51
ENTER CODE:_
v
6 AUX FUNCTIONS
v
61 SET TIME