S2000M MAINTENANCE
GUIDE
33
premises were opening). "AUTOMATIC MODE" indicator demonstrates the current launching
mode (is auto launching mode on or not). "EXTINGUISHING" indicator demonstrates status of
launching (that is no launching, launching delay, launching or launching failure). "S2000–PT"
devices have some buttons for automatic mode controlling (turn on/off auto extinguishing mode)
and for remote launching or canceling of auto extinguishing equipment launch. "S2000–PT"
device is supplied by input for Touch Memory reader, with Touch Memory keys being used for
getting access control to extinguishing area controlling by means of buttons. Touch Memory
keys have to be recorded into the console configuration with authority level allowing
extinguishing area controlling with the corresponding rights. If the user has no rights the
controlling by means of buttons is impossible. "S2000–PT" may be supplied with inner password
for extinguishing area controlling, without Touch Memory key identification. It can be used
when "S2000–PT" unit is located in secured place. The password (PIN-code) can be recorded to
"S2000–PT" device by means of "uprog.exe" program. This password with authority level
allowing extinguishing area controlling has to be recorded to "S2000
М
" console.
The console allows controlling the additional relay outputs, such as annunciators
common for several areas or common extinguishing installation. Refer to the 2.1.7.4 section of
this manual for procedures for relay output control settings.
2.1.7.10
Using the console with sprinkler or drencher extinguishing units based on
devices "POTOK-3N"
The console can be used for displaying the status of sprinkler or drencher fire
extinguishing system via the indication units "S2000–BI(01)".
The indication unit "S2000–BI(01)" is designed to display only one area of fire
extinguishing. The extinguishing area is represented by the pump station, one or two duty
pumps, standby pump and jockey pump. Create the partition for pump station and one partition
for each pump when configuring the console.
Include "Potok–3N" device zones controlling the status of pump station into the pump
station partition and zones controlling the status of pumps into the pump ones. For the first duty
pump use zone
№
1 (which controls turning on/off and pump faults), zone
№
11 (controls the
power outages) and zone
№
21 (automatic control mode). For the second duty pump use zones
with the numbers 2, 12 and 22 respectively, for the standby pump use the numbers 3, 13, 23 and
finally for jockey pump use the numbers 4, 14 and 24. Depending on "Potok–3N" device
configuration some pumps may be absent and the corresponding zones controlling such pumps
might be displayed as "Disconnected alarm loop" status. So don’t create any partition for lacking
pumps. The pump station itself is controlled by zones number 30 – 39 with specific zones
numbers being depended on "Potok–3N" device configuration. For example, zone
№
32
(responsible for manual launching) is used only for systems without pressure. To display the
statuses of the pump station and each pump LED four-indicators of "S2000–BI(01)" are
assigned. By means of program "uprog.exe" designate the partition number for each indicator
group of "S2000–BI(01)" in so manner that the appointment of the partition being corresponded
with the caption on the facial label.
2.1.7.11
Using the console with the phone communicator "S2000-IT"
In order to adjust the devices "S2000–IT" for message transmission from alarm system
the console should be configured to transfer event messages to these devices. Refer to the 2.1.7.5
section of this manual for descripton of configuring of event reporting. The messages contain the
information about loop arming and disarming by specific users provided that the passwords or