S2000M MAINTENANCE
GUIDE
11
Number
Program name
Program description
26
‘Turn off for a given
time when auxiliary
alarm’
If at least one zone is in the state ‘Auxiliary alarm’, then
OFF for a given time;
else ON output.
27
‘Turn on when
disarmed’
If at least one zone is disarmed, then ON;
else OFF output.
28
‘Turn off when
disarmed’
If at least one zone is disarmed, then OFF;
else ON output.
29
‘Turn on when armed’
If at least one zone is armed, then ON;
else OFF output.
30
‘Turn off when armed’
If at least one zone is armed, then OFF;
else ON output.
31
‘Turn on when auxiliary
alarm’
If at least one zone is in the state ‘Auxiliary alarm’, then
ON;
else OFF output.
32
‘Turn off when auxiliary
alarm’
If at least one zone is in the state ‘Auxiliary alarm’, then
OFF;
else ON output.
33
‘ASPT-1’
ON for a given time, if at least one zone in partition have
‘Fire alarm’ status and there are no zones having states
"Auxiliary alarm", "Relay disconnected", "Open relay
output", "Relay output short circuit". When the failure
removed the relay output will be ON
34
‘ASPT-A’
ON for a given time, if at least two zones in partition have
‘Fire alarm’ status and there are no zones having states
"Auxiliary alarm", "Relay disconnected", "Open relay
output", "Relay output short circuit". When the failure
removed the relay output will not be on
35
‘ASPT-A1’
ON for a given time, if at least one zone in partition have
‘Fire alarm’ status and there are no zones having states
"Auxiliary alarm", "Relay disconnected", "Open relay
output", "Relay output short circuit". When the failure
removed the relay output will not be on
36
"Turn on with
temperature increasing"
ON for a given time when the temperature has exceeded
"temperature high" threshold (in “High temperature”
status);
else OFF output.
37
" Turn on with
temperature decreasing "
ON for a given time when the temperature has being below
"temperature low" threshold (in “Low temperature” status);
else OFF output.
38
"Turn on during
launching delay"
ON for a given time during launching delay counting
before automatic fire extinguishing system starting (in
"Launching delay" state);
else OFF.
39
"Turn on during
launching"
ON for a given time if launching pulse for automatic fire
extinguishing system has been given ("Launching" state);
else OFF.
40
"Turn on during
extinguishing"
ON if launching has been confirmed (in "Extinguishing"
state);
else OFF.