FIRE AND ALARM CONSOLE
46
Type password.
Select ‘SERVICE’ menu item by ‘
4
’, ‘
3
’ and ‘ENT’ keys, or
press hot key ‘6’.
Select ‘CANCEL ALARM’ menu item by ‘
4
’, ‘
3
’ and ‘ENT’
keys, or press hot key ‘5’.
During execution of this operation the console cancels all alarm messages. Of course, all alarm
messages leave in console event buffer and can be viewed or printed.
2.2.4
Device and console programming functions
Programming functions are designed for configuring console and intrusion and fire alarm
panelss. This function is protected by password and is available for user having engineer
password (password number 1). To get access to programming functions press key ‘PRG’ and
input engineer password. Enter from 1 to 8 password digits and press key ‘ENT’. If password is
correct, console displays message ‘
PROGRAMMING
’ and grants access to functions. To return
from programming mode into time displaying mode use button ‘CLR’. Panel automatically exits
from programming mode after 2 min if there were no key pressimgs during this time.
Console provides such functions as time setting and clock correction, setting console
date, changing device network address, programming and changing addresses of 2-wire devices,
setting console parameters, password setting, personal computer programming.
2.2.4.1
Date and time settings and clock correction
Time setting
Enter the programming menu (press button ‘PRG’).
Type engineer password.
Select ‘CLOCK SETUP’ menu item by ‘
4
’, ‘
3
’ and ‘ENT’
keys, or press hot key ‘1’.
Select ‘SET TIME’ menu item by ‘
4
’, ‘
3
’ and ‘ENT’ keys, or
press hot key ‘1’.
LCD displays current time in format HH:MM (hours and
minutes). Input new time.
Clock correction
Clock correction allows time correcting for clock accuracy adjustment. The correction
value can be varied in range -120
÷
+120 seconds and will be added to the current time during
every day with discreteness 1 s. For example, if console clock is known to be 5 seconds slow per
day, it should enter the correction value being equal to +5.
Enter in programming menu (press button ‘PRG’).
Type enginner password.
Select ‘CLOCK SETUP’ menu item by ‘
4
’, ‘
3
’ and ‘ENT’
keys, or press hot key ‘1’.
Select ‘CALIBRATION VAL’ menu item by ‘
4
’, ‘
3
’ and
‘ENT’ keys, or press hot key ‘2’.
ENTER CODE:_
v
65 CANCEL ALARM
v
6 SERVICE
ENTER CODE:_
v
1 CLOCK SETUP
TIME: HH:MM
v
SET TIME
v
1 CLOCK SETUP
v
CALIBRATION VAL
ENTER CODE:_