S2000M MAINTENANCE
GUIDE
35
2.2.1
Displaying, viewing and printing device messages
Console receives messages from device. They include event name, data (number and text
partition description, device address, number of alarm loops, reader, relay, user identificator),
and time.
At LCD message indication in top line message name is displayed, and in bottom its
source. Console messages arein the appendix C. As a source, depending on the message type and
console configuration, partition name, alarm loop name, user name device address alarm loop
number, user number, partition number can be displayed. Additional message information can be
seen at pressure corresponded digit. Key ‘
0
’ is used viewing message time and date. Data and
time format is next: DD.NM HH:MM:SS, where DD - day, NM – month number, HH - hour,
MM - minutes, SS - seconds. If since event rise and until its receiving by console considerable
time left (for example, device work independently), the message is shown according to the inner
device clock. Indicator of device time is symbol ‘*’ instead ‘.’ as day and month separator. Also
device time cannot include data
If main message displays text information about message source, key ‘
1
’ shows data in
digit way: partition number, device address and alarm loop number for messages about ALs,
device, reader, user numbers for access messages, partition and user numbers for partition
arm/disarm messages.
When keys ‘
2
’ pressed, console shows text description of partition and loop. If partition
has not text description, when key ‘
2
’ pressed panel show partition number, device address and
alarm loop number.
When keys ‘
3
’ pressed, console shows user name. if text user password description is not
given, console show its database number when key ‘
3
’ pressed.
Pressing key ‘
9
’, Message number in console buffer can be shown. The last message has
number 1, the oldest - 1023.
To print event log console output one message in the line. Next information is printed:
дата
и
event number (format is identical LCD message format), full message name, message
source (device address, number of alarm loop, reader or relay), partition number (name) and text
description, user text description (name). Data prints like table. After each 50 messages table
heading is printing. It has the following view:
|------------------------------------------------------------------------------|
| Date Time | Event |Device |Part# Description| User |
|------------------------------------------------------------------------------|
The displaying and printering information depends on event type.
Zone messages such as alarms, fires, arming, disarming, faults and so on have the
following format, e.g, ‘intrusion alarm’:
On LCD:
INTRUSION ALARM
Corridor 1-floor
, where ‘Corridor 1-floor’ is partition name.
Console shows message data and time if button ‘0’ pressed:
20.12
17:41:11
,
where 20.12 is the day and month (20 December), 17:41:11
is the time (17 hours, 41 minutes, 11 seconds).
At button ‘1’ pressure message name with source message is displayed in digit view:
INTRUSION ALARM
100 002/007
, where 100 is the partition number, 002 is the device address and
007 is the number of alarm loop.
When button ‘2’ is pressed the partition and zone descriptions are displayed:
Corridor 1-floor