S2000M MAINTENANCE
GUIDE
5
1.1.5
Console may logically group alarm loops in
partitions
.
Partition is a set of alarm
loop that is controlled as one unit. This gives next advantages:
−
Arm/disarm require fewer users actions take less time, and probability of operators
mistake is decreased also. If need to arm the large number of ALs, especially if there are ALs of
different devices, joining the alarm loop give very significant event;
−
User can arm/disarm just partitions, authorized to him;
−
Partition arm/disarm can be controlled not only at console, but also at connected
‘S2000-K’ and ‘S2000-4’ devices;
−
New opportunity to organize the system outputs (relay’s) is added;
−
‘S2000-BI’ units can be used for partitions state indication.
There are the restrictions:
−
Number of alarm loop, that can be included in partitions, is limited;
−
Console has to be configured with help of personal computer.
1.1.6
Console allows group partitions in the groups. Partitions group can be controlled
(Arm/disarm), and also display their states on indication ‘S2000-BI’ blocks and LED ‘S2000-
KS’ keyboards.
1.1.7 Console allows one to control by partition arm/disarm and to view their states.
Access to the functions is password protected (PIN-code, Touch Memory key or Proximity card).
Partitions that authorized to user, and partition control rights (arm/disarm permission), are
determined by level of its password. Console indicates arm/disarm operation result. Partition
control possible both at console (PIN-code), and at connected to console ‘S2000-K’ keyboards
(PIN-code) and devices’S2000-4’ (Touch Memory key or Proximity card).
1.1.8
Console may use ‘S2000-BI’ devices for partitions state indication.
1.1.9
Console synchronizes time and date in devices. It is necessary for normal time
window operability in ‘S2000-4’ and ‘S2000-2’ devices. Console provides connection between
‘S2000-2’ device. It is necessary for normal operability network Anti pass back mode (second
passing prohibition) in access control system on the basis of ‘S2000-2’ devices.
1.1.10
Console controls by ‘S2000-SP1’ device relay outputs. These output we will call
system outputs (in opposite to the alarm panel local outputs, controlled by devices itself). System
output reaction depends on state of connected partitions and control program. System relay
outputs can be used for control by light and sound notificators, operational device switching, alarm
message transmitting to the CGP. Except ‘S2000-SP1’ device outputs ‘S2000-KPB’, ‘S2000-4’,
‘Signal-20P’ and ‘Signal-20’ series 02 device outputs can be used as system outputs.
1.1.11
Console allows changing connected through RS-485 interface device addresses,
and also programming and changing address expanders addresses ‘S2000-AP1’, ‘ S2000-AP2’
and address notificators ‘IPR 513-3A’, ‘S2000-SMK’, ‘DIP-34A ver.01’, ‘S2000-IP ver.01’,
connected to the ‘S2000-KDL’ controller two wired connection line. Programming functions are
protected by password.
1.1.12
Console figured for 24-hour work.
1.1.13
Console must be protected from action of atmospheric condensations and
mechanical damage.
1.1.14
Temperature range for console is from 274 to 313
К
(from +1 to +40
О
С
).
1.2
Specifications
1.2.1
Voltage of direct current power supply of the console is from 10,2 to 28,4 V.
1.2.2
Consumed current in standby mode is: if supply voltage 12 V - 70 mA, if supply
voltage is 24 V - 35 mA.
1.2.3
Liquid crystal two line indicator, 16 symbols in the line, with green highlight.