background image

 

Fire Alarm Systems | FMR‑7036 Fire Annunciator Keypad

FMR‑7036 Fire Annunciator Keypad

 

www.boschsecurity.com

 

 

 

u

Compatible with FPD‑7024 Fire Alarm Control Panel

u

Two‑line, 16‑character LCD display

u

On‑board LEDs indicate Silenced, Trouble, Alarm,
and Supervisory

u

Silence and Reset buttons

u

Built‑in keyswitch

The FMR‑7036 is a four‑wire LCD annunciator keypad
used with the FPD‑7024 Fire Alarm Control Panel
(FACP) to establish the location of a fire alarm. The
two‑line, 16‑character display is capable of showing all
messages normally displayed on the control panel. All
alarm and status messages are included. Four
on‑board LEDs provide easy reading of the
annunciator's status from a distance. There are Silence
and Reset buttons for controlling annunciator and
control panel operation. A built‑in keyswitch offers
extra security by locking the annunciator to prevent
unwanted sounder silencing or control panel resetting.

Certifications and Approvals

Region

Certification

USA

UL

UOXX: Control Unit Accessories, System

(ANSI/UL 864)

FM

CSFM

7165-1615:0227

FDNY-

CoA

#6024

Installation/Configuration Notes

Compatible Products

Category

Product ID

Product Description

Control Panels

FPD‑7024

Four‑zone FACP

Mounting

The FMR‑7036 can be surface mounted on a standard
three‑gang box, or with the mounting backplate
provided.

Wiring Guidelines

For the FPD‑7024 FACP, the maximum allowed DC
current draw from the option bus is 500 mA for
keypads. The maximum length of wire (all branches
added together) that can be connected to the option
bus terminals is 4000 ft (1220 m).
The maximum length between any one device and the
control panel terminals depends on the current draw
on the branch that the device is on. The current draw
on a particular branch can be found by adding
together the individual current draws of each device
connected to the branch.

Reviews: